Wilo Stratos 1.5x3-40 Instrucciones De Instalación Y Funcionamiento página 34

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

English
Table I
Problem
Pump does not run
with switched on
power
Noisy pump operation
10.3 Error messages: Error LED "permanent light"
Code
Symbol
No.
flashing
E04
Supply
terminal
E05
Supply
terminal
E10
Motor
E20
Motor
E21
Motor
E23
Motor
E25
Motor
E30
Module
E31
Module
E36
Module
34
cause
Electric fuse faulty,
Pump has no power
Cavitation due to insufficient
admission pressure
Problem
Mains undervoltage
Mains overvoltage
Pump blocked
winding overheated
Motor overload
Short circuit/contact
fault
Contact error
Excess temperature
module
Excess temperature
power component
Module faulty
Subject to technical alterations!
remedies
Check fuse
Rectify interruption to power
Increase system admission
pressure within permissible
range
cause
Mains overloaded
e.g. sedimentation
Motor overloaded
Ambient
temperature to high
Sediment in the
pump
Motor defect
Module not correctly
installed
Air intake to module
heat sink is blocked
Ambient
temperature to high
Electronic
components faulty
remedies
Check electrical
installation
Check electrical
installation
De-blocking routine
starts automatically.
Should this not remove
the blockage, the
pump switches off
after 10 sec.
Call customer services
Let motor cool down,
check the settings
Reduce water
temperature
Call customer services
Call customer services
Reinstall module
Free air intake
Improve ventilation in
room
Call customer service /
swap module
WILO AG 05/2007

Publicidad

Tabla de contenido
loading

Tabla de contenido