Design of the cables
The cables used must comply with the approvals required for the location (e.g. UL).
ƒ
The effectiveness of a shielded cable is reached by:
ƒ
– Providing a good shield connection through large−surface shield contact.
– Using only braided shields with low shield resistance made of tin−plated or
nickel−plated copper braid.
– Using braided shields with an overlap rate > 70 % and an overlap angle of 90 °.
– Keeping unshielded cable ends as short as possible.
Use system cables or shielded cables for these connections:
Analog signals (inputs and outputs)
ƒ
System bus CAN
ƒ
Resolver
ƒ
Encoder
ƒ
The following connections need not be shielded:
24 V supply
ƒ
Digital signals (inputs and outputs)
ƒ
I
Tip!
Parameter setting and configuration can be carried out using the
L−force »Engineer«. For this purpose the Online Help and the Software Manual
for the standard device will guide you.
EDK94ASH24 DE/EN/FR/ES/IT 8.0
Wiring of the standard device
l
8
71