AFTER BEING
STOPPED, A PUMP IN
THE SET DOES NOT
START AGAIN.
THE MOTOR OF AN
ELECTROPUMP IN THE
SET IS VIBRATING.
1.
Motor protection fuses burnt out.
2.
No current is reaching the coil of the respective
remote control switch.
3.
Remote control switch coil interrupted.
4.
The system pressure is not reaching the
respective control pressure switch.
5.
Faulty control pressure switch.
1.
A motor protection fuse has burnt out.
2.
Fuse holder base slack or faulty.
3.
Contacts of the respective remote control
4.
switch worn or faulty.
5.
Pump blocked.
6.
Bearings worn.
Electric wires broken.
ENGLISH
1.
2.
3.
4.
5.
1.
2.
3.
4.
5.
6.
60
Change them.
Use a tester to check the electric circuit
as far as the coil itself and repair any
inter-ruption found.
Change it.
Remove it and clean the connecting
sleeve.
Change it.
Change it.
Secure it if slack. Change it if faulty.
Change the remote control switch.
Free it.
Change them.
Check and repair them.