Genius SPRINT 03 Manual Del Usuario página 19

Ocultar thumbs Ver también para SPRINT 03:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 39
5.4. TERMINAL BOARD CN4
5.4.1. t
otAl opening
"COM2 – OPEN A" terminals. Normally open contact. Connect, to these terminals,
any pulse generator (push-button, key selector, etc...) which by closing a contact,
generates a total opening or closing impulse of the gate. The operation of this contact
is defined by operating parameter "D", see paragraph 9.
• A total opening impulse always has priority over pedestrian opening.
• To connect several pulse generators, connect the devices in parallel.
5.4.2. p
edestriAn opening
"COM2 – OPEN B" terminals. Normally open contact. Connect, to these terminals, any
pulse generator (e.g. push-button, key selector, etc...) which, by closing a contact,
generates a partial opening or closing impulse of the gate. Opening for pedestrians
corresponds to 30% of the memory-stored total opening.
• A total opening impulse always has priority over pedestrian opening.
• To connect several pulse generators, connect the devices in parallel.
5.4.3. s
top
"COM2 – STOP" terminals. Normally closed contact. Connect, to these terminals, any safety device (e.g. pressure
switch, edge etc...), which, by opening a contact, causes the gate to stop immediately and disables any automatic
function. The status of this input is signalled by LED "STOP". The gate resumes its memory-stored cycle only by means
of another total or partial opening pulse.
• If no STOP devices are connected, jumper connect the input.
• To connect several STOP commands, connect the devices in series.
5.4.4. c
losing sAFety deVices
"COM2 – FSW CL" terminals. Normally closed contact. Connect, to these terminals, any safety device (photocell, safety
edge, pressure switch etc...) which, by opening a contact, affects the gate's closing motion, causing it to reverse to
the opening position. The status of this input is signalled by LED "FSW CL".
5.4.5. o
pening sAFety deVices
"COM2 – FSW OP" terminals. Normally closed contact. Connect, to these terminals, any safety device (photocell, safety
edge, pressure switch etc...) which, by opening a contact, affects the gate's opening motion, causing it to reverse to
the closing position. The status of this input is signalled by LED "FSW OP".
•For correct connection of safety devices, consult the following images:
7

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

Sprint 04

Tabla de contenido