EN54 2-8 Zone Conventional Fire Panel - User Manual
6.3
Delay On/Off
Delay countdown pattern of flashing follows buzzer - unaffected by MUTE
BUZZER. Last 5 secs of delay, pulsing of buzzer doubles to warn of
imminent delay end.
1
2
7
Maintenance
Create a log book with reference data (see below) and event data (refer to page
layout at back of this manual). Use this log book to record all maintenance test
results and details of any faults or problems that arise. Enter details of the maintaining
company. The responsible person should ensure that functional tests are performed
daily, weekly, quarterly and annually: daily - check for normal operation; weekly -
testing of at least one sensor/MCP/zone to check panel and audible alarms; quarterly
checks - log book entries/actions, battery state/charger voltage, remote manned
centre links plus perform weekly tests; annually - test all devices and perform visual
inspection of cable fittings and equipment.
Reference Data
Name & Address ....................................................................................
Responsible person ................................................................................
.................................................................................. Date ...................
.................................................................................. Date ...................
.................................................................................. Date ...................
.................................................................................. Date ...................
The system was installed by ...................................................................
and maintained by ......................................... Tele. No. .........................
Cleaning
The panel case may be cleaned periodically by wiping with a soft, damp
lint-free cloth. Do not use solvents.
997-493-002-2, Issue 2
1 Insert and turn key
clockwise to enable access
Level 2 controls.
2 Press
LED lights.
3 Turn the key
clockwise: retuns you to
access Level 1 and saves
selection.
steady.
4 To
procedure to extinguish
LED.
6
90°
. The DELAY ON
90° anti-
LED is lit
cancel,
repeat