UPS
CONFIGURATION
Configurations which can be modified by the user from the control panel are listed in the table below.
FUNCTION
Language*
Output voltage
Buzzer
Operating mode**
Battery low **
Date and time**
* Press keys F1 and F4 simultaneously for t > 2 sec. and English will automatically be reset.
** Function modification can be blocked by means of the configuration software.
Configurations which can be modified by means of configuration software available at service centres are listed in the following
table.
FUNCTION
Operating mode
Output voltage
Output nominal frequency
Autorestart
Auto power off
Buzzer Reduced
EnergyShare off
Timer
Autonomy limitation
Maximum load
94
DESCRIPTION
Selects mimic panel language
language
Selects the rated output
voltage
(Phase - Neutral)
Selects the audible alarm
operating mode
Selects one of five different
operating modes
Estimated autonomy time
remaining for "battery low"
warning
UPS internal watch setup
Selects one of five different operating modes
Selects the rated output frequency
Waiting time for automatic power-on after the return of mains
Automatic UPS power-off in battery operation mode if the
Selects the audible alarm operating mode
Selects the auxiliary socket operating mode
Programmed UPS power on/off (daily)
DEFAULT
• English
• Italian
English
• German
• French
• 220V
230V
• 230V
• 240V
• Normal
Reduced
• Reduced: does not sound due to the
momentary intervention of the bypass
• ON LINE
• ECO
ON LINE
• SMART ACTIVE
• STAND-BY OFF
3 min.
• 1 ÷ 7 @1 min step
DESCRIPTION
Selects the rated output voltage
(Phase - Neutral)
voltage
charge is lower than 5%
Maximum battery operation time
Selects the user overload limit
POSSIBLE CONFIGURATIONS
• Spanish
• Polish
• Russian
• Chinese
DEFAULT
ON LINE
230V
50Hz
5 sec.
Disabled
Reduced
Always connected
Disabled
Disabled
Disabled