QS System Low-Voltage Control Wiring

• System communication uses Class 2 /
PELV low-voltage wiring.
• Follow all local and national electrical
codes when installing Class 2 / PELV
wiring with line voltage/mains wiring.
• Each terminal accepts up to two 1,0 mm
(#18 AWG) wires.
• Total length of control link must not
exceed 610 m (2 000 ft.).
• Make all connections in the control unit's
wallbox.
• A QS system can have up to 100 zones
and 100 devices (see table below).
• Wiring can be T-tapped or daisy-chained.
• Wire sizes:
- Two 1,0 mm
2
(#18 AWG) conductors for
control power.
- One twisted, shielded pair of 1,0 mm
(#22 AWG) for data link.
- Cable is available from Lutron:
GRX-CBL-346S-500 (non-plenum)
GRX-PCBL346S-500 (plenum rated).
Check compatibility in your area.
System Limits
QS Device
3-zone QS
LUTRON
4-zone QS
LUTRON
6-zone QS
LUTRON
seeTouch QS
LUTRON
Sivoia QS
QS smart power supply panel
R
T-Tap Wiring Example
2
QS smart
power
supply panel
Sivoia QS
2
Daisy-Chain Wiring Example
GRAFIK Eye QS
LUTRON
Zone Count
Device Count
3
1
4
1
6
1
0
1
1
1
0
1
GRAFIK Eye QS
seeTouch QS
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
LUTRON
Sivoia QS
LUTRON
LUTRON
GRAFIK Eye
QS System Installation and Operation Guide 5
®
LUTRON
seeTouch QS
LUTRON
LUTRON
QS smart power
supply panel
LUTRON
LUTRON

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Qsg-3pceQsg-4pceQsg-6pce

Tabla de contenido