Concrete Slab
At the appropriate location, construct a concrete slab:
49"
10.5"
7"
14.25"
9.5"
B
38"
C
D
E
Slab Top VIew
• 28 day compression strength of 3000 psi (200 MPa)
• Minimum 5 inches thick
• Minimum 6 inches wider than enclosure on all sides
(shown as D in figure)
• Strengthen slab with No. 6 reinforcing bars (on
12" centers) or 8 ga. steel wire fabric (6" centers).
NOTE: Avoid placing reinforcement in entrance
stub-up area (B).
Attach unit to slab at four corner locations (A) with minimum
5/16" diameter (8mm) masonry anchor bolts long enough to
secure the unit.
The fuel inlet location (C) and the exhaust opening (E) are
shown for reference.
Electrical and Fuel Inlet Locations
A through-slab power cable stub-up is preferred (see
(B) above). If stub-up's are not used, (F) indicates the
recommended location for punching holes for attaching
power conduit. The 1 inch N.P.T. fuel inlet connector (C) is
shown for reference.
7.38"
34.25"
8"
A
78"
94"
F
Lifting the Generator
The generator weighs more than 1,700 pounds (773 kg).
Proper tools, equipment and qualified personnel should be
used in all phases of handling and moving the generator.
WARNING Hazardous Voltage - Contact with power
lines can cause electric shock or burn.
Lifting Hazard / Heavy Object - Can cause
muscle strain or back injury.
•
If lifting or hoisting equipment is used, DO NOT contact
any power lines.
•
DO NOT lift or move generator without assistance.
•
Use lifting pipes as described in
The unit may shift on the lifting pipes during movement,
which can cause injury.
•
DO NOT lift unit by roof as damage to generator
will occur.
Two 60" lengths of 2" Schedule 40 pipe (G), supplied by the
installer, are required to lift the generator onto cement pad.
Insert pipes through the lifting holes (H) located near the
unit's base.
H
Use a spreader bar to ensure that the chains, straps or
cables DO NOT touch the generator's roof. Retouch any
chipped paint with supplied touch-up paint.
C
Lifting the Generator.
G
9