CONTROL PANEL

Installation (SEE PAG. 20)
-
A differential or magnetothermic 10 A switch shall be mounted upstream the
equipment, in order to assure an omni polar separation with a minimum contact opening
of 3 mm.
-
The power supply cables (min 1.5 mm²) shall be separated in comparison with the
signal cables (min 0.5 mm²).
-
Possible contacts connected with the N.C. Inputs shall be arranged in series .
-
Possible contacts connected with the N.O. inputs shall be arranged in parallel.
CONNECTIONS
1-2 : POWER SUPPLY: 230 Vac 50 Hz.
1= PHASE , 2 = NEUTRAL, CN10 = EARTH . ( F1 ) 3A Protection fuse
3-4 : FLASHING LIGHT connection: 230 Vac - 100 W max. ( see Dip 4 and Dip 6 )
5-6-7 : MOTOR connection.
5=opening, 6=closing,7=common. External capacitor connected with Cn8-Cn9 connec-
tors
8-9 : connection ( SELV ) 24 Vac - 5 W max. for ACCESSORIES POWER SUPPLY.
( F3 ) 500 mA protection fuse.
12 - 14 : N.O. input for START command ( see Dip 3 ).
12-13 : N.C. input for detecting devices ( PHOTOELECTRIC CELLS ).
Enabled only when DIP 7=OFF : only during closing, it stops and inverse to a new
opening.
12 -11 : N.C. input for STOP command.
During opening and closing, it stops and it also stops the pause time avoiding a new
automatic closing.
15-16-10 : MOTOR REVOLUTIONS SENSOR.
15 = brown ; 16 = blue ; 10 = black ( see DIP 5 ) .
20-21 : EXTERNAL AERIAL ( 21 = shielding )
WARNING : should you utilize a plug in receiver equipped with its own termi-
nals to be connected with the aerial, do not consider 20-21.
( Dip- Switch Sw1 ) FUNCTIONS PROGRAMMING
Warning : in order to store a new configuration, the power supply shall be
disconnected for a few seconds.
DIP 1
AUTOMATIC CLOSING
OFF = Enabled
ON = Disabled
Dip 2
Functioning with DEAD MAN LOGIC
OFF = Disabled
ON = Enabled. The functioning only occurs through a continuous
activation of the START command (12-14 terminals ). Once the
contact is N.O. again, the movement stops.
Dip 3
Response to repeated START commands (12-14 terminals )
OFF = " Condominium Programme ". OPENING – only when
opening limit switch is activated, - CLOSING - during closing ,
STOPPING and NEW OPENING.
ON = " Step-by-Step Programme " . OPENING - STOPPING -
CLOSING - STOPPING etc...
Dip 4
Functioning of Flashing Light Connection (3-4 terminals )
OFF = Blinking output (a flashing light with fixed light code 70107
shall be utilized ).
ON = Continuous output ( a flashing light code 70106 shall be
utilized).
Dip 5
INDUCTIVE SENSOR enabling
OFF = Motor revolutions calculation enabled during opening and
closing. The device operates in case of impacts against an
obstacle and in this case a stopping as well as a movement
reversal for 2 seconds occur.
position only in versions equipped with inductive sensor ).
ON = DISABLED
Dip 6
2 seconds preflashing
OFF = enabled
ON = disabled
Dip 7
Input enabling for detecting devices (12-13 terminals )
OFF = enabled; only during closing,stops and inverse to a new
opening
ON = disabled
Dip 8 - 9 - 10 :
to be kept in OFF position
( WARNING : set in OFF
.
TRIMMER SETTING
RV1 FORCE : precisely to be set, in order to limit the PUSHING FORCE of the motorized
gate.
RV2 WORK : set to a WORKING TIME exceeding 5-8 seconds the real time of a
complete cycle. Setting with Dip 2 = OFF enabled.
RV3 PAUSE : only with Dip 1 = ON, it allows to set the PAUSE TIME, at the end of this
time the gate will close automatically .
STARTING AND TESTING
With power supply disconnected:
-
Set the Dip-switches according to the functions you wish;
-
Assure that connections have been carried out in a correct way, because a possible
error could damage the equipment in irrepairable way.
With power supply connected :
-
Carefully carry out settings on the trimmers
-
Assure that the red LED relating to N.C. inputs are ON, according to the operator
conditions;
-
Assure that the yellow LED referred to START input only is on in case of operation;
-
Assure that possible safety devices connected with the PHOTO ( 12 -13 ) or STOP
( 11-12 ) inputs are functioning correctly.
-
Assure there is a correct direction ( the first START command after enabling voltage
supply , if the gate is not yet at the opening limit switch, an opening occurs ). If it is not the
case, you shall invert the connections of 5-6 terminals one to the other. When the gate is
open wide, the opening limit switch LED shall be OFF and the closing limit switch LED
shall be ON; when the gate is closed, the closing limit switch LED shall be OFF and the
opening limit switch LED shall be ON.
VERSION WITH INTEGRATED RECEIVER
The equipment version with integrated 433.92 Mhz receiver can function with dip-
switch as well as Roller ( Rolling Code ) transmitters, it can store max 200 different
codes.
Transmitters learning :
Supplying the equipment for the first time, assure that LED DL6 is on ( receiver ready
for storage ).
You only need to press the button of the transmitter in order to store its code in the
receiver ( that button operates as START command ).
The DL6 LED is ON for about 6 seconds and during this time, it is possible to learn
further transmitters belonging to the same category.
The storage phase ends when the DL6 LED is OFF.
To learn further transmitters, you only need to press the P1 ( LEARN ) button, assure
that DL6 LED has been ON, then press the new transmitter button.
Warning : after learning the first remote control, the receiver only accepts other remote
controls belonging to the same category ( DIP or ROLLER).
Total cancellation of stored codes: press the P1 button (DL6 LED is ON ) and keep
it pressed until DL6 LED is OFF .
Releasing the P1 button, the DL6 LED flashes once, then, it is ON again to indicate that
the receiver is ready to learn new transmitters.
ROLLER category remote controls learning without accessing the control
equipment :
when at least one transmitter has already been stored by the above described proce-
dure, it is possible to enable a self-learning of new transmitters belonging to the same
category, without accessing the control equipment .
In fact, you only need to press simultaneously for some seconds buttons 1 and 2 of the
already stored transmitter ( near to the location of the control equipment) then press the
new transmitter button, in order to learn it.
INDUCTIVE SENSOR
The sensor cable n° 2 shall be connected following the combination terminal/
colour: 15 = brown, 16 = blue, 10 = black, then SET DIP 5 ON .
Technical features
Operating temperature : - 20 ÷ + 55
Power supply voltage : 230 Vac ± 5 %
Frequency : 50 - 60 Hz
Accessories power supply connection : 24 Vac max 200 mA
Flashing light connection : 230 Vac max. 100 W
Maximum power to be controlled at the motor connection : 500 W
Electronic torque regulation : min 40 % , max. 98 %
Working time setting : min 5" , max. 90 "
Pause time setting : min. 5", max. 110 ".