Emerson FloBoss™ 103 Flow Manager
Figure 1. FloBoss 103 Flow Manager Nameplate
(ATEX Version shown)
Figure 2. Dual-Variable Sensor Label
Use this safe use instructions (SUI) document with the
FloBoss 103 and FloBoss 104 Flow Manager Instruction
Manual (part D301153X012). For full cautions and
descriptions of installation and troubleshooting
procedures, refer to this manual. If you require training for
this product, contact your local sales office.
The FloBoss 103 Flow Manager with ATEX or IECEx
flameproof approvals may be ordered with optional EIA-
232 (RS-232) communications, dial-up modem
communications, or Dual-Variable Sensor (DVS). It may
not be ordered with a solar panel or a charger board with
Remote Automation Solutions
Safe Use Instructions – Emerson FloBoss 103 Flow Manager
batteries. All options are available on the IECEx type n
version.
FloBoss 103 special conditions for Safe Use
Operating Ambient Temperature: 40°C to +75°C.
Ensure that the thermal fluid transfer does not
overheat the equipment to a temperature
corresponding to the spontaneous combustion
temperature of surrounding gas.
Dual-Variable Sensor special conditions for Safe
Use (X)
The device contains a thin wall diaphragm. During
installation, maintenance, and use take into account the
environmental conditions to which the diaphragm is
subjected. Follow in detail the manufacturer's instructions
for installation and maintenance to assure safety during
the device's expected lifetime.

Declaration of Conformity

Hereby, Remote Automation Solutions declares that the
FloBoss 103 products are in compliance with the essential
requirements and other relevant provisions of European
Directives 2004/108/EC (EMC), 94/9/EC (ATEX), and
97/23/EC (PED).
DANGER
When installing units in a hazardous area, make sure all
installation components selected are labeled for use in
such areas. Installation and maintenance must be
performed only when the area is known to be non-
hazardous. Installation or maintenance in a hazardous
area could result in personal injury or property damage.
Always turn off the power to the FloBoss 103 before you
attempt any type of wiring. Wiring powered equipment
could result in personal injury or property damage.
To avoid circuit damage when working inside the unit, use
appropriate electrostatic discharge precautions, such as
wearing a grounded wrist strap.
Do not exceed the maximum differential and static
pressure ranges listed on the label of the DVS Sensor.
Connecting the FloBoss 103 to a continuous high wattage
power source without removing the battery charger
module may result in battery overcharging and failure. See
Section 3.5.1, Overcharging Potential in the FloBoss 103 and
104 Flow Manager Instruction Manual (part D301153X012).
Do not open covers unless area is known to be non-
hazardous.
Part D301194X012
February 2018