Safe Use Instructions – Emerson FloBoss 103 Flow Manager
Part D301194X012
February 2018
The FloBoss Termination Board connectors use
compression terminals. The input power termination
(CHG+ / CHG-) uses a removable connector and
accommodates wiring up to 1.29 mm (16 AWG) in size. In
all cases, make connections by baring the end (6 mm
maximum) of the wire, inserting the bared end into the
clamp beneath the termination screw, and then
tightening the screw to 0.25 N-m.
Access to wiring connections is via field wiring entries. The
metal pipe plugs provided must remain in place on unused
entries to maintain flame-proof integrity of enclosure. If
these plugs are replaced for any reason, only install
certified plugs or thread adapters that meet or exceed the
product ratings.
DANGER
Do not over torque the connector screws.
Note: Check the input power polarity before turning on
the power.
The inserted wires should have a minimum of bare wire
exposed to prevent short circuits. Allow some slack when
making connections to prevent strain.
The FloBoss 103 accepts input voltages from 8.0 volts to
28 volts at the charge terminals (CHG+ / CHG-) with no
external current limiting (internal current limit is 200 mA).
The terminals are labeled CHG+ for positive power
connection and CHG- for negative power connection on a
label on the termination board. See
Figure 4. Termination Board
6. The FloBoss 103 ships with the NORM/RESET jumper
in the NORM position, and the ON/OFF jumper in the OFF
position.
4
Figure
4.
To apply power to the FloBoss 103:
Unscrew the cover clamp at the base of the front end
cap (LCD end). See
Figure
Figure 5. Cover Clamp Assembly
Unscrew the front end cap cover.
Place the power jumper (located on the LCD if
installed or located at J1 on the Battery Charger Board)
in the ON position. See
A
NORM/RESET Jumper
B
ON/OFF Jumper
Figure 6. Front End of FloBoss 103 (with LCD)
Replace the front end cap cover (LCD end) and cover
clamp.
After the FloBoss 103 completes start-up diagnostics
(RAM and other internal checks), the optional LCD displays
the date and time to indicate that the FloBoss has
completed a valid reset sequence. If the LCD does not
come on, perform trouble-shooting for possible causes
(see
Step
9).
www.Emerson.com/RemoteAutomation