5.2 - MOTORS

CITY1-EVO control unit can control one or two alternate current
asynchronous motors.
During the opening phase, motor M1 is started first, motor M2
starts after the time set for the parameter
During the closure phase, motor M2 is started first, motor M1
starts after the time set for the parameter
The times set for the parameters
avoid the doors colliding. If necessary, change the default values
by accessing the programming menu:
NOTE: If the control unit needs to control one motor only, the
latter must be connected to terminals of motor M1.
1. Connect motor M1 cables as follows:
• opening cable to terminal H6
• closing cable to terminal H8
• common return cable to terminal H7
2. Connect motor M2 (if any) cables as follows:
• opening cable to terminal H3
• closing cable to terminal H5
• common return cable to terminal H4
H1 H2 H3 H4 H5 H6 H7 H8
M2
m
WARNING:
• In case it has not yet fitted, a start capacitor for each motor is
required; connect the start capacitor for motor M1 between
terminals H6 and H8 and start capacitor for motor M2 (if any)
between terminals H3 and H5.
• In case motor M2 is not connected, set menu
r.AP
(opening delay).
r.Ch
(closure delay).
r.AP
r.Ch
and
are used to
M1
t.AP2
to zero.
CONTROL OF THE CORRECT ORDER OF CLOSING
LEAVES
If the control unit detects a wrong overlap order (leaf 1 gets to the
closing position before leaf 2), the gate is opened a little again so
that it can close correctly.
If the leaves do not overlap (e.g. in a double swing gate) set to
zero the opening door delay parameter in order to disable the
control of the right closing order.
HYDRAULIC MOTORS
If hydraulic motors are used, it is necessary that some unit
programming parameters are set out as follows:
• Motor power set at 100%
Pot1
100
=
Pot2
100
=
• Slowdowns are disabled (they are already disabled by default)
rA.AP
no
=
rA.Ch
no
=
• Obstacles sensor disabled
SEnS
no
=

5.3 - STOP

For added safety, you can install a STOP switch that, when
pressed, immediately stops the automation.
The switch must have a normally closed contact, which opens in
case of activation.
• Connect the cables of the STOP switch between terminals
L5 (STOP) and L6 (COM) of the unit.
C
To activate the function, change the settings of
StoP
parameter
L1 L2 L3 L4 L5 L6 L7 L8 L9 L10 L11
NOTE: in case the stop switch is operated while the gate is
open, the automatic closing function will always be disabled. To
close the gate again, you will need a start command (if the start
function in pause is disabled, it will be temporarily enabled to
allow the gate release).
The stop switch function can be activated by means of a remote
control stored on channel 3 (see relevant instructions of MR
receiver).
- 36 -