Installation
Step 3: Test eyewash unit
1. After completing installation, test the eyewash station for proper operation by
pulling down the tray. Check for proper water flow and quickly close the tray.
Visually inspect the eyewash unit weekly for cleanliness and proper solution
level (per ANSI Standard Z358.1-2004). When the water level drops below
the 15-minute fill line, the tank must be emptied and then refilled. To refill the
eyewash tank, follow the procedures outlined in Step 2 found on page 4.
OPTIONAL UNIT WITH HEATER JACKET: Test the unit by pulling the front flap
down and all the way out. This action should activate the water spray. Check
the sprayheads for proper water flow and look for possible water leakage
throughout the unit. Visually inspect all areas of the heater jacket to verify
proper operation of the heating element.
2. Attach the eyewash inspection tag (supplied) to the eyewash unit. This tag is
to be used for weekly inspection documentation. Hook-and-loop fasteners are
provided to attach the tag to the unit.
3. If the eyewash unit is not working properly, remove it from the hazard area and
contact Bradley Corporation immediately.
Tank
Cap
Pedestal

Optional Heater Jacket Junction Box

LED Light

Green Light: an indication that the unit has power.
Amber Light: an indication that the heater is in operation and heating the unit. The light will be on only while the heater is
operating (heating the unit).
Red Light: an indication that the thermostat needs to be reset. To reset the thermostat, follow the procedure outlined
below.
a. Remove the top of the heater jacket.
b. Find the "reset" button on the thermostat (located on the tank) and press the button.
After pressing the button, check to be sure that the red light is off and that the green light is on (the amber light
will be on only if the heater is operating). If the red light is still on, press the "reset" button again.
c.
Replace the top of the heater jacket.
Bradley Corporation • 215-1546 Rev. E; ECM 09-05-0003
Position the heater pad evenly
around the drain hole. Do not
block the drain hole.
Clamp
Latch
Drain Hole