Descargar Imprimir esta página

Publicidad

Idiomas disponibles

Idiomas disponibles

Enlaces rápidos

Installation
Faucet-Mount Eyewash
Model S19-200B
Read this installation manual completed to ensure
proper installation, then file it with the owner or
Installation
maintenance department. Compliance and conformity
to drain requirements and other local codes and
ordinances is the responsibility of the installer.
Separate parts from packaging and make sure all
Packing List
parts are accounted for before discarding packaging
TH
IS
material.
SI DE
UP
The ANSI Z358.1 standard requires an uninterrupted
supply of flushing fluid. Bradley plumbed emergency
fixtures require a minimum of 30 PSI (0.21 MPa)
flowing pressure. Flushing fluid should be tepid per
ANSI Z358.1.
The inspection and testing results of this equipment
should be recorded weekly to verify proper operation.
This equipment should be inspected annually to
ensure compliance with ANSI Z358.1.
For questions regarding the operation or installation
of this product, visit bradleycorp.com or call
800-BRADLEY (272.3539). Product warranties and
parts information may be found under "Products" on
our website at bradleycorp.com.
P.O. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
Supplies Required
Wrench
Cold or tempered water supply (minimum 30 PSIG)
To ensure uninterrupted water flow to the fixture, water supply to
the eyewash from the faucet must be on at all times. This can be
accomplished by removing the faucet handles, if applicable.
Standard or gooseneck faucet with outlet threads:
55/64" x 27 thread (male)
15/16" x 27 thread (female)
13/16" x 27 thread (female)
Refer to the original faucet documentation for specific thread size. If
original documentation is not available, contact the faucet manufacturer
directly for thread information.
NOTE: Bradley provides two adapters that convert the standard 55/64" x 27
female threads on the fixture.
If the faucet has an outlet thread of 55/64" x 27 thread (male), then no
adapter is needed.
If the faucet has an outlet thread of 15/16" x 27 thread (female), then
use the 15/16" x 27 thread (male) x 55/64" 27 thread (male) adapter.
If the faucet has an outlet thread of 13/16" x 27 thread (female), then
use the 13/16" x 27 thread (male) x 55/64" 27 thread (male) adapter.
These thread sizes fit most common faucet designs. If one of these adapters
is not compatible with your faucet, see the list below for additional threaded
adapters that may be purchased at an additional cost.
Optional Adapters Available for Purchase
153-395
Faucet not included
153-396
153-401
153-422
153-440
Installing Diverter and Adapter
1
1. Remove the existing aerator from the faucet.
2. Screw the diverter assembly onto the faucet and tighten with a wrench. The
diverter pin must be facing front, toward the user. The shutoff pin should be
90° from the diverter pin.
To prevent scratches on the adapter, it is recommended to place a
grip pad or cloth around the diverter and adapter while tightening.
Installing and Using the Eyewash
2
1. Remove the Allen screw from the bushing on the eyewash yoke assembly.
2. Attach the yoke assembly to the connection on the diverter assembly.
Sprayheads should be facing the user's eyes.
3. Reinstall the Allen screw. Be sure yoke assembly is firmly attached to the
adapter.
When adjusting the eyewash yoke assembly while attached to
diverter assembly, always remember to loosen the Allen screw
before making adjustments and then retighten.
4. Activate the eyewash by pulling the diverter pin towards you to ensure
that the eyewash is working properly.
To activate the faucet only, push the shutoff pin until water flows
from the faucet.
bradleycorp.com
Female, 3/16" x 24 - Chrome
Male, 3/8" IPS - Chrome
Female, 3/4" (Garden Hose) - Chrome
Male, 13/16" x 28 - Chrome
Female, 3/4" x 27 - Chrome
S19-200B Parts List
6
5
2
Shutoff
Pin
4
7
Diverter
Pin
Item
Part No.
Qty.
1
107-371
2
Dust Covers
2
S90-350
1
Yoke Assembly
3
130-140
1
Allen Wrench
4
160-131
1
Set Screw
5
S27-290
1
Diverter Assembly
6
S65-154
1
Threaded Adapter Kit
7
S27-296
1
Shutoff
8*
S65-153
1
Gasket Kit
9*
204-486
1
Emergency Sign
10*
204-421
1
Inspection Tag
*Not Shown
215-1333 Rev. H; ECN 13-16-01B
1
3
Description
© 2013 Bradley
8/28/2013
Page 1 of 3

Publicidad

loading

Resumen de contenidos para Bradley S19-200B

  • Página 1 Refer to the original faucet documentation for specific thread size. If original documentation is not available, contact the faucet manufacturer directly for thread information. NOTE: Bradley provides two adapters that convert the standard 55/64" x 27 female threads on the fixture. •...
  • Página 2 Voir le filetage spécifique dans la documentation d’origine du robinet. Si cette documentation n’est pas disponible, se renseigner sur le filetage directement auprès du fabricant du robinet. REMARQUE : Bradley fournit deux adaptateurs qui se monte sur le filetage femelle standard de 55/64 po x 27 de l’appareil. •...
  • Página 3 Si la documentación original no está disponible, comuníquese directamente con el fabricante de la llave para obtener información sobre la llave. NOTA: Bradley proporciona dos adaptadores que convierten las roscas hembra estándar de 55/64" x 27 en el accesorio. •...