Charging of refrigerant
Keeping the valve of the outdoor unit closed, be sure to charge the liquid refrigerant into the service port at the
liquid side.
If the specified amount of refrigerant cannot be charged, fully open the valves of the outdoor unit at liquid and
gas sides, operate the air conditioner in COOL mode, and then charge refrigerant into service port at the gas
side. In this time, choke the refrigerant slightly by operating the valve of the canister to charge liquid refrigerant.
The liquid refrigerant may be charged suddenly, therefore be sure to charge refrigerant gradually.
33-EN
1114208701-1 EN PT ES.indb 17
1114208701-1 EN PT ES.indb 17
C (Corrective amount
Combined outdoor units (HP)
of refrigerant) (kg)
–
–
–
1.5
–
–
–
2.5
–
–
–
3.5
–
–
–
8.5
–
–
–
10.5
8HP
–
–
0.0
10HP
–
–
3.0
10HP
–
–
5.0
12HP
–
–
7.5
10HP
–
–
8.5
12HP
–
–
9.5
14HP
–
–
11.5
16HP
–
–
12.5
12HP
10HP
–
3.0
12HP
12HP
–
4.0
12HP
10HP
–
6.0
12HP
12HP
–
7.0
14HP
12HP
–
8.0
16HP
12HP
–
10.0
16HP
14HP
–
12.0
16HP
16HP
–
14.0
8HP
–
–
0.0
8HP
8HP
–
-4.0
8HP
8HP
–
-4.0
10HP
8HP
–
-2.0
10HP
10HP
–
0.0
8HP
8HP
8HP
-6.0
8HP
8HP
8HP
-6.0
10HP
8HP
8HP
-6.0
10HP
10HP
8HP
-6.0
10HP
10HP
10HP
-5.0
10HP
10HP
10HP
-4.0
12HP
10HP
10HP
-2.0
12HP
12HP
10HP
0.0
12HP
12HP
12HP
2.0
– 17 –
Full opening of the valve
Open the valves of the outdoor unit fully.
MAP080
MAP100
MAP120
Packed valve
Using a 4mm-hexagonal wrench,
fully open the valve rods.
Liquid side
Balance packed valve
Balance pipe
Using a 4mm-hexagonal wrench, fully open the valve rods.
Ball valve
Using a wrench, turn it counterclockwise by 90° until it hits the stopper.
(Full open)
Gas side
MAP140
MAP160
Ball valve
Using a flathead screwdriver, turn it counterclockwise by 90° until it hits the
stopper. (Full open)
Position of screwdriver slot
Service
port
Valve unit
Fully closed
Fully opened
Using flathead
screwdriver, turn it
counterclockwise by
90° until it hits the
(1)
stopper. (Full open)
Slot
(2)
Flare nut
*
When opened fully, do not apply
excessive torque after the screwdriver hits
the stopper; otherwise a problem may be
caused on the valve. (5
Fully opened
Fully closed
or less)