Accessory Parts - Toshiba MMY-MAP0804HT5P Manual De Instalación

Ocultar thumbs Ver también para MMY-MAP0804HT5P:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Relocation
Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the
air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and/or
vibration may result.
When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe. Disconnecting
the refrigerant pipe with the service valve left open and the compressor still operating will cause air or other gas to be sucked
in, raising the pressure inside the refrigeration cycle to an abnormally high level, and possibly resulting in rupture, injury or
other trouble.
Never recover the refrigerant into the outdoor unit. Be sure to use a refrigerant recovery machine to recover the refrigerant
when moving or repairing. It is impossible to recover the refrigerant into the outdoor unit. Refrigerant recovery into the
outdoor unit may result in serious accidents such as explosion of the unit, injury or other accidents.
(*1) Refer to the "Definition of Qualified Installer or Qualified Service Person."
CAUTION
New refrigerant air conditioner installation
This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer.
The characteristics of R410A refrigerant are; easy to absorb water, oxidizing membrane or oil, and its pressure is approx.
1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil has also been changed.
Therefore, during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the
refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the
main unit and installation tools are changed from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A).
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
To disconnect the appliance from main power supply.
This appliance must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm.
The installation fuse (all type can be used) must be used for the power supply line of this conditioner.
Do not wash air conditioners with pressure washers. Electric leaks may cause electric shocks or fires.
7-EN
1114208701-1 EN PT ES.indb 4
1114208701-1 EN PT ES.indb 4
2

Accessory parts

P
a
t r
n
a
m
e
Q
'
y t
S
h
a
p
Owner's Manual
1
Installation Manual
1
Attached pipe
1
(for Ø22.2)
Attached pipe
1
(for Ø28.6)
– 4 –
e
U
s
a
g
e
(Be sure to hand it to the customers.)
(Be sure to hand it to the customers.)
Connecting pipe for gas side piping
(MAP080, MAP100 type)
Connecting pipe for gas side piping
(MAP120, MAP140, MAP160 type)
EN
ID
ID
8-EN
02/27/14 1:39 PM
02/27/14 1:39 PM

Hide quick links:

Publicidad

Tabla de contenido
loading

Tabla de contenido