INSTALLATION
INSTALLATION
Mounting Bracket for CIR 400-2 O
13 3/16˝
1 9/16˝
(97)
7 1/2˝
(190)
9. Attach the heater bracket to the mounting bracket (outermost
hole), using the bolt, lock washer and nut supplied. Tighten
securely.
10. The bracket attached to the top of the heater allows rotation up
to 45° on the short axis by loosening the attachment bolt.
11. Once heater position is established, tighten all nuts and bolts at
mounting and heater bracket connections to maintain the heater
in a secure and stable position.
12. Read and follow all warnings, and the following section on
Operation to enjoy safe operation of the heater.
9.7
Power supply
DANGER Electrocution!
Carry out all electrical connection and installation
work in accordance with all national, state and local
building code.
DANGER Electrocution!
Each 240 V heater must be wired directly to a circuit
with a timer switch and the proper size breaker and
wire gauge.
DANGER Electrocution!
Do not plug models CIR 200-2 O or CIR 400-2 O into
a wall outlet.
The specified voltage on the nameplate must match
the voltage at the circuit breaker panel.
Electrical connection must be performed by a qualified electrical
tradesperson. Installation must conform with the latest edition
Electrical Code ANSI/NFPA N0 70 in the U.S.A. and PART 1 CSA
C22.1 in Canada.
10
|SUNWARMTH
™
CIR INFRARED HEATER
1 9/16˝
(40)
(40)
1/2˝
(13)
8
M8
8
1 1/4˝
(32)
9.7.1
CIR 150-1 I and CIR 150-1 O
Plug heater into a properly grounded wall outlet connected to a
120 V, 60Hz, 15 Amp copper wire circuit that is properly grounded
and controlled by a timer switch.
9.7.2
CIR 200-2 O
Using 12 AWG copper wire, connect the heater to a 240 V, 60Hz,
15 Amp circuit breaker that is properly grounded and controlled
by a timer switch.
9.7.3 CIR 400-2 O
Using 12 AWG copper wire, connect the heater with a timer switch
to each of two independent 240 V, 60Hz, 15 Amp circuit breakers
that are each properly grounded.
Ø8
WWW.STIEBEL-ELTRON-USA.COM