Slowing down time
In case this function is enabled, during the last seconds of motion, the
control unit will give motor a reduced power command, to avoid a
strong impact with the stop end. t.AP is the max. allowed time.
WARNING:
• In case the self-learning function of working times is NOT used, we
recommend disabling the slowing down function in order to
measure both opening and closing times, and to enable it again
once the setup has been carried out. The control unit will
automatically consider the working time delay caused by the
slowing down.
• If partial opening time t.APP is shorter than t.AP, there will be no
slowing down during the pedestrian cycle opening.
Fast closing time after slowing down
If a slowing time other than 0 is set up, it could be likely that the gate
speed is not enough for the lock to fasten during the closing phase.
In case this function is enabled, once the slowing down phase is
finished, the control unit will give a normal speed command (that is to
say, with no slowing down) for the set up time, and then it will open
the gate for a second fraction, to avoid leaving the motor under stress.
WARNING: in case the gate has no electric lock, set the value 0.
Start command during the opening phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the opening phase.
PAUS
The gate stops and goes to pause
ChiU
The gate immediately starts closing
no
The gate go on with the opening phase (command is ignored)
Select option PAUS, to set up the "step-by-step" operation logic.
Select option 'no', to set up the 'always open' operation logic.
Start command during the closing phase
This menu allows fixing the control unit conduct in case it receives a
Start command during the closing phase.
StoP
The gate stops and its cycle is considered as finished
APEr
The gate opens again
Select option StoP, to set up the "step-by-step" operation logic.
Select option APEr, to set up the 'always open' operation logic.