To adjust braking length in both opening and closing phases, proceed as follows:
1) Close or open the gate (make sure that the closing/opening limit switch is pressed).
2) Move DIP 1 to ON (DIP 2-3-4-5-6=OFF)
3) Send PP control signal (through Step-by-Step Input or memorised remote control). The gate starts opening
at normal speed.
4) When the gate reaches the desired braking point, send another PP control signal, the gate will start braking
until it is completely opened. Subsequent PP control signals will be ignored.
5) With totally open and stopped gate, send a PP control signal (through Step-by-Step Input or memorised
remote control) The gate starts closing at normal speed.
6) When the gate reaches the desired braking point, send another PP control signal, the gate will start braking
until it is completely closed. Subsequent PP control signals will be ignored.
7) Move DIP1 to OFF again.
NOTE:
-
if braking length does not require any adjustment in both opening and closing, leave the gate to totally
open/close without sending a PP control signal to start braking.
-
If safety functions (STOP and PHOT) are activated, the adjustment procedure will be blocked. Repeat the
procedure from the beginning.
-
During this phase, the anti-crash sensor is disabled.
-
if the Encoder device is installed, the anti-crushing sensor is disabled during the acquisition phase.
To set the control unit to function without slowdowns (timed operation regulated by TW trimmer), proceed as
follows:
1) Move the gate to an intermediate position, far from the limit switches
2) Move DIP 1 to ON (DIP 2-3-4-5-6=OFF)
3) Give the Step/Step command through the PP input or remote control
4) The flashing LEDs will confirm the initiated reset
5) When the LEDs turn off, move DIP 1 to OFF
The control unit has deleted data relative to the stroke and slowdowns.
With all DIPs on ON, the control unit switches to SERVICE MAN mode.
The PHOT input has the CLOSE push-button function (connect the button with N.O. contact).
The PP input has the OPEN push-button function (connect the button with N.O. contact).
The OPEN/CLOSE push-buttons must be kept pressed during operation. The opening of the STOP input
stops the motor.
The contemporary pressure of OPEN/CLOSE stops the motor.
When DIP1 is moved to ON, the board indicates that the torque has been applied during a number of
flashes (from 1 to 4) of the DL2 green LED, followed by a 3-s interval.
The max torque is indicated with DL2 green LED with fixed light.
To increase the torque, press P1. The DL2 LED changes the number of flashes to indicate the selected
torque value.
Once the desired torque is selected, move DIP 1 to OFF to memorise this presetting.
STROKE ACQUISITION & SLOWDOWNS
RESET STROKE ACQUISITION & SLOWDOWNS
SERVICE MAN MODE
ADJUSTMENT OF THE TORQUE (DIP1:ON)