Wire connections shown in Fig. 1 are described hereunder:
Terminals
L-N-GND
MOT-COM-MOT
N-BLINK
SWO
SWC
PHOT (CLOSE)
STOP
COM
P.P. (OPEN)
24 VAC
SCA
ENC1
SHIELD-ANT
Note:
The control unit uses a "P2" key with the same functions of the Step-by-Step push-button. This is useful
to control the automatic system during installation (only with DIP2: OFF).
1) Cut off power supply.
2) Manually release the door, move it at around half stroke and lock it again.
3) Reset power supply.
4) Send the step-by-step (P.P.) control signal through the P2 key, P.P. or remote control.
5) The door leaves should open. If not, with stopped motor, it is sufficient to invert the move wires of the
motor (MOT/MOT) of the motor and the limit switches (SWO/SWC).
6) Proceed with regulations described in "STROKE ACQUISITION & SLOWDOWNS"
CONTROL PANEL CP.MS5
Function
Description
Input, 230VAC 50Hz (CP.MS5)
Power supply
Input, 115VAC 50/60Hz (CP.MS5 115V))
(1-Phase/2-Neutral/GND-Ground connection)
Connection to motor:
Motor
(MOT-move/COM-Common/MOT-move)
Output, connection to Flashing light
LAMP
CP.MS5: 230 Vac 40W max.
CP.MS5 115V: 115 Vac 40W max.
SWO
Input, OPENING limit switch (Normally Closed contact)
SWC
Input, CLOSING limit switch (Normally Closed contact)
Input, connection to safety devices, Normally Closed (N.C.) contact
(e.g. photocells): configurable through DIP3).
PHOT
In "Service man" mode, it activates the CLOSE function. In this
case connect a Normally Open (N.O.) key.
Input, STOP key (N.C. contact)
STOP
Can assume the Close or Pedestrian function (contact N.O.) see
"Advanced Programming" paragraph.
COM
Common, all control inputs.
Input, step-by-step key (N.O. contact).
Can assume the OPEN function see paragraph "Advanced Pro-
Step-by-Step
gramming".
In "Service man" mode, it activates the OPEN control function.
24Vac
Output, 24Vac/200mA max accessory power supply.
Contact free from voltage, not insulated for the connection of open
gate indicator lamp.
SCA
Open contact with closed door leaf. Flashing light during the door
leaf movement. With open door leaf, the contact is closed.
Input, connection of the encoder (OPTIONAL).
ENCODER
See section HOW TO ADJUST BRAKING
Connection of the antenna to the incorporated radio-receiver module
Antenna
(SHIELD-screen/ANT-signal).
CHECKING CONNECTIONS:
WIRE DIAGRAM
11