4a
• Ensure 1 1/4 in (32 mm) of
heating cable is exposed above
end seal strain relief.
• Mark heating cable jacket.
• Lightly score jacket around
and up as shown.
• Peel off jacket.
• Determine heating cable type
and continue as shown.
BTV, QTVR
XTV, KTV
BTV, QTVR
XTV, KTV
Strain
1 1/4"
relief
(32 mm)
5/8"
(16 mm)
Do not cut
bus wires.
Go to Step 5a
Go to Step 5b
E-100-LR Light Retrofit Installation Instructions
4b
• Ensure 1 1/8 in (28 mm)
of heating cable is exposed
above end seal strain relief.
The conductor should remain
staggered.
• Lightly score jacket around
and up as shown.
• Peel off jacket.
• Unwind heating element, cut
and remove as shown.
• Lightly score clear jacket
around and up as shown.
• Peel off jacket.
• Remove insulation from
ends of bus wires.
Note: Core sealer is not used
on VPL. Discard core sealer.
Skip Step 5 and go to Step 6
Strip length guide for VPL
mm
10
20
in.
1
VPL
1 1/8"
1/2"
(28 mm)
(13 mm)
Strain
relief
Do not cut
1/4"
bus wires.
(6 mm)
1/4"
(6 mm)
1/2"
1/2"
(13 mm)
(13 mm)
30
40
50
60
2
3
70
80
80
3