Descargar Imprimir esta página

Main Components - Lamborghini Caloreclima ECO 5N Manual Para La Instalación Y El Mantenimiento

Quemadores para gasóleo

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

By pressing it for more than 3 seconds, the diagnosis stage will be activated (red light flashes rapidly). The
table below describes the causes of the lock out or fault in relation to the number of flashes (always red).
The diagnosis function is interrupted by pressing the release button for at least 3 seconds.

MAIN COMPONENTS

ECO 5N - 5RN - 5LN
3
2
1
1009DIS391
INDEX
1
Components Plate
2
Electromagnetic Valve
3
Connection Flange
4
Photoresistance
5
Release Button
6
Electrodes set
Nozzle Line (with Preheater Mod. R)
7
Automatic air flap
8
DIAGNOSIS OF LMO EQUIPMENT FAULTS AND LOCK OUT
Description of operating anomalies
Visual indication
Possible causes
2 flashes
No flame signal
4 4
-
-
-
-
3 flashes
Not used
4 4 4
4 flashes
Stray light on ignition
4 4 4 4
5 flashes
Not used
4 4 4 4 4
6 flashes
Not used
4 4 4 4 4 4
7 flashes
No flame signal during operation
4 4 4 4 4 4 4
-
-
-
8 flashes
Anomalies in fuel preheating time
4 4 4 4 4 4 4 4
9 flashes
Not used
4 4 4 4 4 4 4 4 4
10 flashes
Incorrect electrical connection or damage to equipment
4 4 4 4 4 4 4 4 4 4
4
5
Faulty fuel valves
Faulty flame detector
Incorrect burner setting, no fuel
No ignition
Faulty fuel valves
Faulty flame detector
Incorrect burner setting, no fuel
6 7
16
15
13
14
12
9 Control box
10 Pump
11 Motor
12 Body
13 Fan
14 Deflector
15 Transformer
16 Draught tube
8
9
1009DIS205
22
10
11

Publicidad

loading

Este manual también es adecuado para:

Eco 5rnEco 5ln