Overview Of Iec Pelv Wiring - Lutron GRAFIK Eye QS Guía De Instalación Rápida

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 25
Wiring the GRAFIK Eye

Overview of IEC PELV Wiring

IR Wiring
1.0 mm
2
each terminal
From external
IR connection
(by others)
Contact Closure Input Wiring
24 V
50 mA
For settings, see the full installation
and operation guide at
www.lutron.com/qs
Example:
Occupancy sensor
1.0 mm
(maximum 1)
each terminal
®
QS with DALI Control Unit:
®
1: IR DATA
2: IR COM
A: CCI SIG
B: 24 V
C: CCI COM
QS Link Control Wiring
24 V
Common and power (terminals 1 and 2):
Two 1.0 mm
2
Two 4.0 mm
To control stations,
window treatments,
or other GRAFIK Eye
QS control units
Data (terminals 3 and 4):
Twisted, shielded pair 0.5 mm
each terminal
For additional information, see the complete installation and operation guide at www.lutron.com/qs
GRAFIK Eye
1 2 3 4 5 6 L N
100 mA
each terminal (for link <153 m)
2
each terminal (for link 153 to 610 m)
2
1 2 3 4 5 6 L N
®
2
QS with DALI Control Unit Quick Installation and Operation Guide 6
®
1: COM
2: 24 V
*
* Do not connect terminal 2
3: MUX
between any GRAFIK Eye
4: MUX
control unit and any other power
supply, including another GRAFIK
Eye
QS control unit.
®
See "Power Group Wiring" for a
detailed wiring example.
Note: Use appropriate wire connecting
devices as specified by local
codes.
QS
®
N H 1 2 3

Publicidad

Tabla de contenido
loading

Tabla de contenido