High starter voltage alarm
7.2.5
This setting is only available if the Aux input has been set to "Starter battery".
When enabled, the alarm will activate when starter battery voltage rises above the set value for more than 10
seconds. The alarm will deactivate when the starter battery voltage drops below the clear value.
Default setting
Range
Disabled
Disabled /
enabled
When enabled
Default setting
Set value
1.1V
Clear value
1.0V
7.2.6
Midpoint deviation alarm
This setting is only available if the Aux input has been set to "Midpoint".
When enabled, the alarm will activate when the midpoint voltage deviation rises above the set value for more
than 10 seconds. The alarm will deactivate when the midpoint voltage deviation drops below the clear value.
Default setting
Range
Disabled
Disabled /
enabled
When enabled
Default setting
Set value
2%
Clear value
1%
7.2.7
High temperature alarm
This setting is only available if the Aux input has been set to "Temperature".
When enabled, the alarm will activate when the battery temperature rises above the set value for more than 10
seconds. The alarm will deactivate when the battery temperature drops below the clear value.
Default setting
Range
Disabled
Disabled /
enabled
When enabled
Default
setting
Set value
2°C (2°F)
Clear value
1°C (2°F)
7.2.8
Low temperature alarm
This setting is only available if the Aux input has been set to "Temperature".
When enabled, the alarm will activate when the battery temperature falls below the set value for more than 10
seconds. The alarm will deactivate when the battery temperature rises above the clear value.
Default setting
Range
Disabled
Disabled /
enabled
23
0 - 95.0V
0.1V
0 - 95.0V
0.1V
0 – 99%
1%
0 – 99%
1%
Range
-99 - +99°C (-146 -
+210°F)
-99 - +99°C (-146 -
+210°F)
Step size
1°C (1°F)
1°C (1°F)