INSTALLATION AND MAINTENANCE INSTRUCTIONS
MI-SC6
Six Supervised Control Module
SPECIFICATIONS
Normal Operating Voltage:
Stand-By Current:
Alarm Current:
Temperature Range:
Humidity:
Dimensions:
Accessories:
Wire Gauge:
Maximum Monitored Output Circuit
Wiring Resistance:
Table 1:
CURRENT RATING
3A
2A
1A
.5A
BEFORE INSTALLING
This information is included as a quick reference installation
guide. Refer to the appropriate control panel installation manual
for detailed system information. If the modules will be installed in
an existing operational system, inform the operator and local au-
thority that the system will be temporarily out of service. Discon-
nect the power to the control panel before installing the modules.
This system contains static sensitive components. Always ground
yourself with a proper wrist strap before handling any circuits so
that static charges are removed from the body. The housing cabi-
net should be metallic and suitably grounded.
NOTICE: This manual should be left with the owner/user of
this equipment.
GENERAL DESCRIPTION
The MI-SC6 Six Supervised Control Module is intended for use in
an intelligent alarm system. Each module is intended for switch-
ing applications involving DC which require wiring supervision.
A common SLC input is used for all modules. Each module has
its own address. A pair of rotary code switches is used to set the
address of the first module from 01 to 94. The remaining mod-
ules are automatically assigned to the next five higher addresses.
Provisions are included for disabling a maximum of three unused
modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled green LED indicators. The panel can
cause the LEDs to blink, latch on, or latch off.
Each module has terminals for connection to an external supply
circuit for powering devices on its Monitored Output Circuit.
Each supply must be power limited and its voltage/current limits
must be at or below those specified in Table 1.
There is a short circuit protection monitor for each module. This
is provided to protect the external power supply against short cir-
cuit conditions on the Monitored Output Circuit.
M450-01-00
15-32VDC
2.25 mA
35 mA (assumes all six relays have been switched
once and all six LEDs solid on)
-10°C to 55°C
10 to 93% Non-condensing
17.3cm H x 14.7cm W x 3.2cm D
Suitably grounded metallic cabinet
0.9mm2 - 3.25mm2
40 Ohms
MAXIMUM VOLTAGE
LOAD DESCRIPTION
30VDC
30VDC
30VDC
30VDC
Included:
Shipped on Board:
(1)
(6)
(6)
(3)
NOTE: Three shunts on Sync Generator MUST NOT be removed.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a
listed compatible control panel.
The MI-SC6 Module shall be mounted in a suitably grounded
Metallic Cabinet for EMC compliance.
1
Resistive
Resistive
Inductive (L/R = 2ms)
Inductive (L/R = 2ms)
(7) 1 × 4 Terminal Blocks
(2) 32mm Stand offs
(4) Screws
(5) Short Power Supply Jumpers
(2) Nuts
(1) Long Power Supply Jumper
Small shunt
Large shunts on Enable Power Supply Monitors
Large shunts on Disable Short Circuit Protection
Large shunts on Sync Generator
by Honeywell
Morley IAS Fire Systems
Charles Avenue
Burgess Hill, West Sussex, RH15 9UF
APPLICATION
Steady
Pulsing
Pulsing
Pulsing
(15) Large Shunts
(2) Small Shunts
(6) 47k Ohm End of Line Resistor
(2) EOL Relay
Connector Assembly
C0905-00
I56-2956-000