Franklin Electric 214753 Serie Manual De Instrucciones De Montaje Y Servicio página 4

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 15
Disposal
Observe the local, regional and national
regulations and dispose of any control gear
accordingly. This product contains electrical
and electronic components and should be
disposed of accordingly.
5.
parameters
The tables below summarize the technical
ters of the 3-wire Control box range. Models
characteristics, detailed capacitor sizes and
motor currents. The connector terminals are
suitable for copper (Cu) wire.
Power ratings and model numbers
Motor
Motor
Control Box
Rating
Mod. No.
Mod. No.
[kW]
0,25
214753****
2803552115
0,37
214755****
0,55
214757**** 2803572115
0,75
214758**** 2803582115
Rated currents and wire sizing – use
Copper (Cu)
Motor
Max. Start
Current
1
Rating
Current
[A]
[kW]
0,25
2,8
0,37
4,0
0,55
5,9
0,75
7,3
Notes:
1. Nominal supply current at nominal voltage.
2. Motor starting current under nominal
conditions.
3. Use external junction box for drop cable
sizes larger than 6 mm
6.
Installation Procedure
Before Installation
box current rating
corresponds with the
Information!
GB
Mechanical installation
Your control box should be mounted to a ver-
-
Electrical installation
Any electrical system such as described in
this manual must only be installed by profes-
Start-
Capacitor
48
65
95
Electrical wiring diagram
switching device are shown inside the Con-
Maximum
trol Box housing. All connections must be
lead
2
checked if the installation was not commissi-
diameter
[A]
oned by you:
[mm
]
2
1. TURN OFF AC POWER AT THE SOUR-
9,7
6
13,7
6
2. Remove the enclosure lid.
21,6
6
27,8
6
3. Connect the incoming 230V AC power
.
2
4. Connect the motor to the control box.
5. Tighten all screw terminals
6. Replace the enclosure lid
7. Turn on AC power at source (distribution
7. Operation
Normal operation
Control box is equipped with relay, for con-
trolling motor start and operation indepen-
dently. No further adjustments necessary.
Avoid mounting the
equipment in direct
sunlight, near open
pressurized water or other
Information!
liquids. Take the necessary
environmental conditions
into consideration.
Life threatening voltage.
Make sure that nobody
can switch on the power
unexpectedly while work
Danger!
is being carried out.
Make sure that multiple
earth-points are avoi-
ded. Refer to the local
standards and norms for
Danger!
borehole installations
CE (DISTRIBUTION BOARD)
Built-in capacitor can carry
dangerous voltages even
after disconnecting from
grid power. Use appropriate
Warning!
resistors to discharge
capacitors before servicing.
supply to the control box as shown in the
wiring diagram (Figure A)
board)
4

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

214755 serie214757 serie214758 serie

Tabla de contenido