CHIUDE= CLOSE button input (n.o. contact).
(25,26) ANT.= Input of radio board antenna
(27,28) RX 2CH.= Radio board 2nd channel contact (n.o. contact).
Dip-switch functions
N.B.:
Every change of functions have to be done without electricity
DSW1= This selects the type of functioning of the P.P. button and Remote control.
Off= "OPEN" - "STOP" - "CLOSE" functioning
On= "OPEN" - "CLOSE" - "OPEN" functioning.
DSW2= This enables or disables the automatic re-closing - "TCA TRIMMER".
Off= Automatic re-closing enabled
On= Automatic re-closing disabled
DSW3= This enables or disables the apartment building function (after the first opening command, the
P.P. button and the Remote control are deactivated).
Off= Apartment building function disabled.
On= Apartment building function enabled.
DSW4= This enables or disables the pre-blinking function.
Off= Pre-blinking disabled.
On= Pre-blinking enabled.
DSW5= This enables or disables the ram blow.
Off= Ram blow enabled
On= Ram blow disabled
DSW6= This activates or deactivates slow-down.
Off= Slow-down deactivated
On= Slow-down activated
DSW7= This activates or deactivates the motor starting function.
Off= Motor starting function deactivated
On= Motor starting function activated
DSW8= Spare ... (can be used as customer requires)
Trimmer functions
N.B.:
The "DA.90BM" control unit can operate both with or without limit switches.
If limit switches are not used, the "FCA" and "FCC" inputs should be bridged with the "+V"
common connection and the "TL" and "TLR" trimmers should be calibrated appropriately, in
keeping with the automation stroke time. The fixed courtesy light time is set at 180 sec.
TCA=
This allows the automatic re-closing time to be adjusted when this is enabled by positioning the
DSW2 Dip-switch on OFF.
Adjustment can be from a minimum of 5 to a maximum of 150 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
TL=
This allows the working time of the automation to be adjusted. If the limit switches fail, the soft-
ware protection will intervene after this time has elapsed. (Add about 4 sec. to the actual stroke
time of the automation).
The "TL" time is always added to the "TLR" time and therefore the total working time both dur-
ing opening and closing is obtained from "TL" + "TLR".
Adjustment can be from a minimum of 7 to a maximum of 180 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
TLR=
This allows the adjustment of the duration of slow-down from when the limit switch intervenes.
The "TLR" time is always added to the "TL" time and therefore the total working time both dur-
ing opening and closing is obtained from "TLR" + "TL".
Adjustment can be from a minimum of 1 to a maximum of 6 seconds.
The minimum time is obtained by rotating the trimmer completely clockwise.
7