C
ONNECTIONS TO
Follow the instructions below in order:
open the door
remove the terminal cover panel positioned under the switches (see "Front UPS views" )
connect the protective conductor (ground cable) to the PE marked screw.
connect the input, output and battery cables to the terminal board, observing the positions and polarities indicated in
the figure below. Connect N BATT, N INPUT and N OUTPUT cables to the neutral bar.
Note: PE M6 screw, BATT M10 screw, N M8 screw
Once installation operations have been completed and connections verified (see paragraph "First start-up and initial settings"),
restore the terminal cover panel and close the door.
C
ONNECTIONS TO
Follow the instructions below in order:
open the door
remove the terminal cover panel positioned under the switches (see "Front UPS views" )
connect the protective conductor (ground cable) to the PE marked screw.
connect the input, bypass, output and battery cables to the terminal board, observing the positions and polarities
indicated in the figure below. Connect N BATT, N INPUT and N OUTPUT cables to the neutral bar.
Note: PE M6 screw, BATT M10 screw, N M8 screw
The input and bypass Neutral must always be connected.
The input and bypass lines must be connected to the same potential as of the Neutral.
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
S
E
-HF 100
AFEPOWER
VO
S
E
-HF 100
AFEPOWER
VO
MODEL WITH STANDARD BYPASS
MODEL WITH SEPARATE BYPASS
Pag. 76 di 272 + FR