AS400 P
ORT
PIN #
1
15
2
8
7
4,5,12
6,13,14
9,10
3,11
NOTE: The figure shows contacts present inside the UPS, able to carry a max current of 0.5A at 42Vdc.
The position of the contacts indicated in the figure is without an alarm or signal present.
IV332 Rev.001 SIEL S.p.A.
Data di emissione: 2012-06-04
NAME
TYPE
15V
POWER
GND
POWER
REMOTE ON
INPUT #1
REMOTE OFF
INPUT #2
REMOTE
INPUT #3
BYPASS
BATTERY LOW
OUTPUT #1
BATTERY
OUTPUT #2
WORKING
LOCK
OUTPUT #3
BYPASS
OUTPUT #4
AS400 PORT
Isolated auxiliary power +15V±5% 80mA max
Mass to which isolated power supplies (15V) and remote
controls (Remote ON, Remote BYPASS, Remote OFF) are
Connect pin 2 with pin 15 for at least 3 seconds to switch on
Connect pin 8 to pin 15 and the UPS will immediately switch
Connect pin 7 to pin 15 and power will transfer from the
inverter to the bypass. As long as the UPS is connected,
bypass operation will remain, even if the input mains cut off.
If the jumper is removed in the presence of power, the UPS
will begin operation via the inverter. If the jumper is removed
without power, the UPS will begin operation via batteries
Signals that batteries are low when contact 5/12 is closed
Signals that the UPS is operating via batteries when contact
Signals that the UPS is locked when the contact is closed
Signals that load power is passed through the bypass when
the contact is closed
FUNCTION
referred
the UPS
off
(1)
6/14 is closed
(1)
Pag. 98 di 272 + FR
(1)