6.3.3 Function menu 3: Operate
Operating data and status information are displayed in this
function menu. Settings can be made at the same time, e.g.
choice of control mode and changing the set value.
1
2
• Back to the main menu
1
• Click on "Set value"
2
Continuation of function menu 3, see next page.
→
3
• Click on "Set value..."
3
→
5
6
• Increase/reduce the set
5
value with the cursor keys
• Optimisation for SXE-DXE:
6
• Close slide valve on
discharge side
• Start zero volume
alignment by clicking on
"Optimization".
• The zero volume
alignment causes the
calibration of the pump
curve where Q=0 m
and maximum speed
through measurement of
the motor current and
alignment with the
stored value. The zero
volume alignment
increases the measuring
accuracy of the
hydraulic operating data
and is necessary once
when commissioning for
the first time.
• Back to the function
7
menu
26
7
3
/h