INSTALLATION INSTRUCTIONS FOR FEDERAL MODEL SST-MV
A. General
The Federal Signal Model SST-MV is a solid-state signalling device that can be used for
general purpose signalling. Any one of four distinctive signalling tones may be selected
by the installation of the J4 or J5 plugs in the appropriate positions. The tone can easily
be changed if the signalling requirements change. The Model SST-MV can be installed
either indoors or outdoors. The SST-MV is listed at Underwriters Laboratories, File
E4813 (Category UCST) Contl. #558H. The SST-MV is also cUL listed.
B. Specifications
Operating Voltage
Operating Current
Sound Output
Wail
Yelp
Horn
Temporal Slow Whoop
Weight (approx.)
Dimensions (HWD)
C. Unpacking
After unpacking the unit, examine it carefully for damage that may have occurred in
transit. If the equipment has been damaged, file a claim immediately with the carrier,
stating the extent of the damage. Before proceeding, ensure that the parts listed in the
KIT CONTENTS LIST have been supplied.
D. Kit Contents List
Quantity
1
1
1
E. Installation
People's lives depend on safe installation of our products. It is important to follow all
instructions shipped with the products. This device is to be installed by a trained electrician
who is thoroughly familiar with the National Electrical Code and will follow the NEC
Guidelines as well as local codes.
The selection of the mounting location for the device, its controls and the routing of the
wiring is to be accomplished under the direction of the Facilities Engineer and the Safety
engineer. In addition, listed below are some other important safety instructions and
precautions you should follow:
SELECTABLE SIRENTONE-MULTI VOLT
Description
Adapter
Gasket, Adapter
Connector Plug, 4-Position
SAFETY MESSAGE TO INSTALLERS
120/240 Vac 50-60 Hz, 24 Vdc
Voltage
120 Vac
240 Vac
24 Vdc
dB(A) @ 10 ft
on Axis
109.5
111
107
110.5
4.4 lb (2.173 kg)
14.5 in x 12 in x 9 in
-1-
Current
210 mA
120 mA
600 mA
dB(A)
UL Rating
100
100
94
Part Number
K8476121-04
K8476122
K140340