Electrical connection
Electric supply must correspond to that indicated on the appliance.
Connection cables have to be sized according to appliance power and installation
requirements.
Informational values:
Heat pump
PAC 16
PAC 22
PAC 31
* cable size for lengths of up to 25 m
These data are only indicatives, you must ask an electrician to determine the
exact data for your pool installation.
Power supply must be equipped with a 30 mA differential protection.
Use the cable glands and grommets provided inside the heat pump to route
cables.
As this machine is installed outdoors, connections must be made standard cable
routed in protective conduit at a depth of 50 cm.
The heat pump only functions when water flow is present.
It is therefore imperative to control flow with the filtration system pump by using
electrical clock of the pool system.
Regime
Cable size
monophasis
3 x 2.5mm²*
monophasis
3 x 4mm²*
triphasis
5 x 2.5mm²*
Maximum input
amperage
10A
16A
10A
25
Head of power
supply line
protection
16A
20A
16A x 3 or
16A triphasis