HAND/OFF/AUTO Operation
14:33
14:32
PIDval2
PIDval2
61.7PSI
61.7PSI
Hz Out
Hz Out
57.63Hz
0.00Hz
I Out
I Out
0.00A
0.00A
S T F
———
FWD
STOP
EXT
EXT
PREV
PREV
SET
SET
NEXT
NEXT
VARIO
speed
®
HAND
OFF AUTO
HAND position
The pump will run immediately. The motor speed is controlled manually by adjusting the Hand Speed setting.
WARNING! Only operate in HAND momentarily and under close supervision. The pump will not shut off in HAND
and may cause damage and/or injury.
OFF position
The pump will not run
AUTO position
The pump will not run if the pressure is above the set pressure. The pump will run if the pressure drops below the Set
Pressure less the Start Pressure. Example if the set pressure is 40PSI (P.133=40 PSI), and the Start Pressure is 5PSI
(P.577=1005). The pump will start when the pressure drops below 35PSI (see example below). The pump will stop
automatically (SLEEP mode) when the set pressure is met and the motor speed is low.
4
PULL
LCD
14:33
PIDval2
61.7PSI
Hz Out
57.63Hz
I Out
0.00A
STF
FWD
EXT
PREV
SET
NEXT
HAND/OFF/AUTO 3 position selector switch.
Sec.
FWD indication is ON when
the pump is running.
STOP indication is on when
the pump is not running
VARIOspeed
®
LCD Quick Start Manual