CPV..-GE-ASI-...
3
Addressing the AS-i valve terminal type 10
3.1 Assign the AS-i slave address
We recommend the use of the Festo addresser ASI-PRG-ADR
part no. 18959 with adapter cable part no. 18960 (or Siemens
PSG)
Before connecting an AS-i slave to the bus, assign a non-
reserved AS-i address to each AS-i slave. Set the desired ad-
dress with the AS-i addresser. Permitted range 1 ... 31.
Please note:
–
The factory setting of the terminal is address 00
–
ID code and IO code see type plate on the terminal
–
It is not necessary to parametrize the AS-i slaves
3.2 Output addresses of the solenoid coils (top view)
Terminal with 2 double valves
9708A
2
4
1
3
Terminal with 4 single valves
1
2
3
4
13