NOTICE If communication does not begin upon placing the
generator in AUTO, installing batteries, and pressing System
Update, the monitor may need to be re-linked. To link, follow
Steps 3 through 6.
3. Locate the MENU AND ESCAPE buttons on the
control panel (A). Press and hold for 3 seconds to
enter the linking mode.
4. "LINKING MODE" will scroll across the generator
control panel.
5. Locate and hold the SYSTEM UPDATE button (B) on
the wireless monitor for 5 seconds. All 3 LEDs will
flash until the monitor links to the generator. Once it
links, the monitor will display the current state. The
monitor will try to link for 1 minute. (This step can only
be completed when the generator is in Linking Mode).
6. Once the link has been confirmed, press the OK
button on the generator control panel to exit or the
control board will turn off linking after 5 minutes. The
generator will now communicate with the wireless
monitor.
NOTICE It may take up to 1 minute for the monitor to begin
displaying the generator status correctly.