Wireless Monitor Troubleshooting - Briggs & Stratton FORTRESS Manual De Instalación Y Operación

Generador de reserva monofásico enfriado por aire
Ocultar thumbs Ver también para FORTRESS:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Wireless Monitor Troubleshooting

Problem
Monitor not flashing status LED's
Linking error
Wireless communication lost
Service Needed red LED flashing
58
Cause
1. Batteries inserted incorrectly
2. Low battery power
3. Conditions too bright to see flashes
4. Communication from generator is
within 10 minute update sequence
5. Immersed in liquid
6. Monitor not linked.
1. Generator control board not in
"Linking Mode"
2. Monitor "System Update" button
not pressed for 5 seconds during
generator control board "Linking
Mode"
1. Monitor is too far from generator
2. Building materials are blocking
wireless signal (i.e. - steel studs,
aluminum siding, radiant barrier foil
insulation)
1. Generator system needs service
2. Wireless communication lost
3. Linking error
Correction
1. Verify correct battery orientation
2. Replace batteries
3. Move monitor to a less lit area
4. Press "System Update" button
5. Allow to dry for 24 hours, replace
batteries. If problem persists
order Wireless Monitor (part
number 316196GS)
6. Follow linking procedure.
1. On generator control board
press and hold the MENU and
ESCAPE buttons for 3 seconds
until "Linking Mode" scrolls
across screen. Press and hold
"System Update" button on
Monitor for 5 seconds.
2. Press and hold "System Update"
button on Monitor for 5 seconds.
1. Move monitor closer to generator
2. Order Symphony Wireless router
(model 6220) to increase signal
strength
1. Refer to Service code Detection
System in manual
2. See Correction section for
"Wireless communication lost" in
Troubleshooting Guide
3. See Correction section for
"Linking error" in Troubleshooting
Guide

Publicidad

Tabla de contenido
loading

Tabla de contenido