Akron Brass Style 3419 Apollo Instrucciones De Funcionamiento Y Mantenimiento página 6

Monitor pe (eléctrico portátil) con patas rebatibles
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

– PAUSE/ RESUME" switch . The monitor will now oscillate between the left and right limits you have set . To adjust the
oscillation limits, press and hold the "OSCILLATION START/SET – PAUSE/RESUME" switch upwared when moving in the
direction in which you wish to change the limit and release the "OSCILLATION START/SET – PAUSE/RESUME" switch when the
new limit is reached . The nozzle can be raised or lowered during oscillation . To pause oscillation, press the "OSCILLATION
START/SET – PAUSE/ RESUME" switch downward momentarily and release . This will pause the oscillation with the current
position limits . To re-start oscillation, press the "OSCILLATION START/SET – PAUSE/RESUME" switch downward momentarily
and release to resume the oscillation with the current position settings . To cancel oscillation, press the "RIGHT /LEFT" switch
either direction momentarily .
4. DUAL INLET GROUND BASE:
Do not exceed 500 GPM (1900 LPM) with one hose or 800 GPM (3030 LPM) with two hoses, when using a fog nozzle or the following
discharge pressures with straight tips, unless the unit is secured in the direct connect flange base on a truck .
NR-Not Recommended
The following hose arrangement is recommended for this appliance: Use two hoses and bring both hoses straight back from the
siamese parallel to each other . Loosely tie the hoses together 10 feet (3m) from the monitor with a hose and
ladder strap, rope, etc . (See Figure 3)
When the unit is operating in the portable base, do not attempt to move or pick up any part of the base itself or the 10 feet (3m) of
supply hose closest to the unit .
When the unit is stored in direct connect base or truck mount, it is recommended that the nozzle or tips be lowered against a rigid
support or removed during transportation .
Do not use Larger than 3" Hose when using the dual inlet portable base .
Setup Instructions:
Rotate the three front folding legs of the ground base to the full open position . Aim center leg toward target . Set spikes with ham-
mer end of safety chain hook . Ensure lock pins are fully engaged . Aim discharge upward . Secure safety chain to spike driven into the
ground or other object capable of withstanding reaction force of 500 lbs or more . Charge hose slowly . If unit moves while charging,
reset spikes .
Figure 3
TWO HOSES
TIP SIZE
PSI
1-3/8"
100
1-1/2"
100
1-3/4"
70
2"
45
ONE HOSE
kPa
PSI
690
80
690
55
480
NR
310
NR
kPa
550
380
NR
NR