Descargar Imprimir esta página

WEG CFW100 V2.4X Referencia Rápida página 23

Publicidad

Idiomas disponibles

Idiomas disponibles

Fault / Alarm
A136
Alarm indicates that the DeviceNet
Idle Master
network master is in Idle mode.
A137
Alarm that indicates that one or more
DeviceNet
DeviceNet connections timed out.
Connection
Timeout
A163
Analog input signal AI1 at 4 to 20 mA or
Signal Fault AI1
20 to 4 mA is below 4-20 mA.
A700
No communication with remote HMI,
Remote HMI
but here is frequency command or
Communication
reference for this source.
Fault
A702
This failure occurs when there is a
Inverter Disabled
SoftPLC movement block (REF block)
active and the "General Enable"
command is disabled.
A704
It occurs when 2 or more SoftPLC
Two Movem.
movement blocks (REF Block) are
Enabled
enabled at the same time.
A706
This failure occurs when a SoftPLC
Refer. Nao Progr.
movement block is enabled and the
SPLC
speed reference is not programmed for
the SoftPLC.
A712
It occurs when there is an attempt to
SPLC protected
copy the SoftPLC application protected
against copy
against copies.
F021
Undervoltage fault on the intermediate
Undervoltage
circuit.
on the
DC Link
Quick Reference of Parameters, Alarms and Faults
Description
Possible Causes
Set the switch that controls the master operation
of the master for Run or the corresponding bit on
the configuration word of the master software.
If further information is needed, refer to the
documentation of the master used.
Check the network master status.
Check network installation, broken cable or
fault/poor contact on the connections with
the network.
Cable of AI1 broken.
Poor contact at the signal connection on the
terminals.
Check if the communication interface with the
HMI is properly configured in parameter P312.
HMI cable disconnected.
Check if the drive General Enable command
is active.
Check the user's program logic.
Check the programming of the references in the
Local and/or Remote mode (P221 and P222).
Attempt to copy WLP application protected
against copies ("never permit copies").
Attempt to copy WLP from a copy protected
against copies ("no permission to copy from
a copy")
Wrong voltage supply; check if the data on the
inverter label comply with the power supply and
parameter P296.
Supply voltage too low, producing voltage on
the DC link below the minimum value (in P004):
Ud < 200 Vdc in 200 / 240 Vac.
Phase fault in the input.
Fault in the pre-charge circuit.
CFW100 | 23

Publicidad

loading