Quick Reference of Parameters, Alarms and Faults
Fault / Alarm
F236
Fault indicates that the DeviceNet
Idle Master
network master is in Idle mode.
F237
Fault that indicates that one or more
DeviceNet
DeviceNet connections timed out.
Connection
Timeout
F701
No communication with the remote
Remote HMI
HMI; however, there is command or
communication
frequency reference for this source.
fault
F710
No communication with the remote
SPLC Progr.
HMI however, there is no command or
bigger than 5 KB
frequency reference for this source.
F711
The upload or the SoftPLC application
The upload of the
failed.
SoftPLC
application failed
26 | CFW100
Description
Possible Causes
Set the switch that controls the master operation
for Run or the corresponding bit on the
configuration word of the master software.
If further information is needed, refer to the
documentation of the master used.
Check the network master status.
Check network installation, broken cable or
fault/poor contact on the connections with
the network.
Check that the HMI communication interface is
properly configured in parameter P312.
HMI cable disconnected.
Extension of the SoftPLC Prog. exceeded
5 KBytes.
The CPU failed to boot the SoftPLC.
Incompatible application uploaded (P900 = 2)
and command for application (P901 = 0).