Quick Reference of Parameters, Alarms and Faults
Fault / Alarm
F022
Overvoltage fault on the intermediate
Overvoltage on
circuit.
the DC
Link
F031
Main control cannot establish the
Fault of
communication link with accessory.
communication
with the accessory
F033
Stator resistance setting fault P409.
V V W Self-tuning
Fault
F051
Overtemperature fault measured on the
IGBTs
temperature sensor of the power pack.
Overtemperatures
F070
Overcurrent or short-circuit on the
Overcurrent/
output, DC link or braking resistor.
Shortcircuit
F072
Motor overload fault (60 s in 1.5xInom)
Motor Overload
F080
Fault related to the supervision
CPU Fault
algorithm of the inverter main CPU.
(Watchdog)
F081
Fault in the attempt to save the User
Fault on the Save
parameter table.
User function
F082
Fault in the copy of parameters.
Fault in the Copy
Function (MMF)
24 | CFW100
Description
Possible Causes
Wrong voltage supply; check if the data on the
inverter label comply with the power supply and
parameter P296.
Supply voltage is too high, producing voltage on
the DC link above the maximum value (in P004):
Ud > 410 Vdc in 200 / 240 Vac.
Load inertia is too high or deceleration ramp
is too fast.
P151 setting is too high.
Accessory damaged.
Poor connection of the accessory.
Problem in the identification of the accessory;
refer to P027.
Stator resistance value in P409 does not comply
with the inverter power.
Motor connection error; turn off the power
supply and check the motor terminal box and the
connections with the motor terminals.
Motor power too low or too high in relation to
the inverter.
High temperature at IGBTs (P030 > 120 °C).
High ambient temperature around the inverter
(>50 °C (>122 °F)) and high output current.
Blocked or defective fan.
Heatsink is too dirty, preventing the air flow.
Short-circuit between two motor phases.
IGBTs module in short-circuit or damaged.
Start with too short acceleration ramp.
Start with motor spinning without the Flying
Start function.
P156 setting is too low in relation to the motor
operating current.
Overload on the motor shaft.
Electric noise.
Inverter firmware fault.
Attempt to save (P204 = 9) more than 32
parameters (with values different from the
factory default) on the User parameter table.
The function Saves User is blocked.
Attempt to copy the parameters from the Flash
Memory Module to the inverter with different
software versions.