Safety devices
The boiler GASTER 56 N AW is equipped with devices that guarantee safety in case of
operation faults.
Automatic-reset temperature limiter (safety thermostat)
This device prevents the water temperature in the system from exceeding boiling point.
The maximum cut-in temperature is 110°C.
Automatic reset of the temperature limiter can only occur with cooling of the boiler (the
temperature must drop by at least 10°C) and identification and consequent elimination
of the problem that caused the shutdown. The safety thermostat (detail 7 of fig. 1) is lo-
cated inside the control panel.
Fume sensor safety device (fume thermostat)
The boiler is equipped with a fume evacuation control device (fume sensor - ref. 3 of
fig. 1). In case of anomalies in the fume evacuation system with consequent return of
burnt gases in the room, the unit shuts down. The anti-wind hood is equipped with a tem-
perature sensor bulb for measuring and controlling the fume temperature.
Any leakage of burnt gases in the room causes a temperature increase detected by the
bulb, causing the boiler to shut down within 2 minutes and stopping the gas to the burner.
If the fume sensor cuts in, unscrew the protection cover (ref. 3 of fig. 1) located on the
control panel and manually reset the device. The boiler will start working again.
If the sensor has to be replaced due to a failure, only use original accessories and ensure
that the electrical connections and bulb positioning are correctly carried out.
B
THE FUME SENSOR MUST NOT BE CUT OUT FOR ANY REASON!
Opening the front casing
To open the boiler front panel, see the sequence in fig. 4.
fig. 4 - Front panel opening
B
Before carrying out any operation inside the boiler, disconnect the power and
close the gas cock upstream.
14
EN
1
2
cod. 3541A171 - Rev. 01 - 03/2018
Cleaning the boiler and flue
For proper cleaning of the boiler (see fig. 5):
Close the gas cock ahead of the boiler and disconnect the electrical power
Remove the front panel of the boiler (fig. 4).
Lift the casing cover.
Remove the insulation 5 covering the anti-backflow device.
Remove the smoke chamber closing plate.
Remove the burner assembly (see next section).
Clean from the top downwards, using a flue brush. The same operation can be car-
ried out from the bottom upwards.
Clean the fume evacuation ducts between the cast iron elements of the boiler shell
with a vacuum cleaner.
Carefully refit all the previously disassembled parts and check the tightness of the
gas circuit and the combustion ducts.
During cleaning operations take care not to damage the fume thermostat bulb fitted
on the back of the fume chamber.
5
2
3
fig. 5 - Cleaning the boiler
1
Casing cover
2
Smoke chamber closing plate
3
Flue brush
4
Combustion analysis plug
5
Insulation
GASTER 56 N AW
1
4