14. Connect "T/R" and "GND" terminals on transfer switch
control board (B) to the generator's control panel (A)
"TxRx" and "TxRx GND" terminals using #18 AWG
twisted pair copper conductors, no greater than 200 ft
in length, 300 volt 75°C-90°C via ten-pole connector
supplied with generator.
A
15. Tighten all wire connections/fasteners to proper torque.
See label inside transfer switch enclosure for proper
torque values.
Supervisory Control Wiring
An air conditioner can be used with the supervisory contacts
on either terminals A-A or B-B. Terminals A-A can only be
used with supervisory control. Large loads can only be used
with contactor control on terminals B-B. Examples of each
system are described below.
1. The terminal strip on the transfer switch control board
has four connections for customer use. There are two
sets of "Normally Closed" contacts available. They will
be activated when generator power is required. These
can be used for supervisory control of large connected
loads on generator. Loads will be allowed to operate if
there is enough generator power available.
For installer convenience, there are two wireways provided to
help keep supervisory load wires organized.
2. Terminals "A-A" on transfer switch control board
are rated for 24VAC. Connect these contacts in
series between air conditioner thermostat and air
conditioner contactor.
To air conditioner contactor
A
A
From air conditioner thermostat (yellow?)
8
3. Terminals "B-B" on transfer switch control board are
B
B
4. Tighten all wire connections/fasteners to proper torque.
The illustration on the following page shows a typical
completed installation. Your actual layout will vary.
Illustration callouts are:
A - From utility watt-hour meter
B - Current transformers
B
C - Transfer switch
D - T/R and GND to Generator
E - Transfer switch control board
F - Supervisory contacts
G - Wireways
H - Neutral terminal
J - Neutral bus
K - Ground bus
L - Main distribution panel
M - UTILITY 240VAC to Generator
N - Two-pole connector
O - Ten-pole connector
P - Generator
R - Generator circuit breaker
S - Generator Neutral terminal
T - Generator Ground terminal
U - Transfer switch ground terminal
V - Load connection
W - Generator disconnect circuit breaker
X - Utility disconnect circuit breaker
Y - Utility connection
Z - Generator connection
24 VAC
rated for 1 Amp 125 VAC. When connected with an
installer supplied contactor, it can be used to control
a large load, such as an electric hot water heater.
Contacts are connected in series with the contactor
control circuit.
Contactor
See label inside transfer switch enclosure for proper
torque values.
BRIGGSandSTRATTON.COM
Neutral
120 VAC