Flush the system thoroughly before fitting Tank Booster or Tank Booster Pro:
It is critical that all debris is flushed from the pipe-work prior to installing the valve.
Not flushing the system properly is the most common cause of system difficulties.
Check:
Measure and note all site parameters (pressure, temperature, etc.), and check
against the specifications of the chosen valve. If the site conditions are outside
those specified for the valve then they must be rectified prior to installing the
valve.
Valve MUST NOT be subjected to heat during installation as this may damage the
valve internals.
Valve MUST NOT be fitted on steam-supplied systems, but to water systems only.
Valve MUST NOT be frozen. If the valve is installed in a situation where freezing
is a possibility, then suitable insulation must be fitted to prevent damage to the
valve.
DO NOT use excess thread sealant (in liquid, tape or other form) as this may
cause the valve to fail.
TANK BOOSTER
Installation Instructions
IS279 REV L
2-17-16
8