Multi Variable Air Conditioners Duct Type Indoor Unit
3.4 Wiring Requirements
(1) Power Cord Size and Air Switch Capacity
Model
GMV-ND56PHS/A
GMV-ND63PHS/A
GMV-ND71PHS/A
GMV-ND80PHS/A
GMV-ND90PHS/A
GMV-ND100PHS/A
GMV-ND112PHS/A
GMV-ND125PHS/A
GMV-ND140PHS/A
GMV-ND160PHS/A
(1) Use copper wire only as unit's power cord. Operating temperature should be within its rated
value.
(2) If the power cord is more than 15 m (49-1/4 feet) long, please increase properly the sectional
area of power cord to avoid overload, which may cause accident.
(3) Above selection requirements: Power cord size is based on BV single-core wire (2~4pc) at 40°
(104°F) Cambient temperature when laying across plastic pipe. Air switch is D type and used at
40°C (104°F). If actual installation condition varies, please lower the capacity appropriately
according to the specifications of power cord and air switch provided by manufacturer.
(4) Install cut-off device near the unit. The minimum distance between each stage of cut-off device
should be 3 mm (1/8 inch) (The same for both indoor unit and outdoor unit).
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.