SPECIFICATION
Earth Resistance Ranges:
Accuracy (23°C ±2°C):
Total service error:
Compliance with Standards:
Test Frequency:
Test Current:
Interference:
Max. Current Loop Resistance:
30
0,01 Ω to 19,99 Ω
0,1 Ω to 199,9 Ω
1 Ω to 1,999 kΩ
10 Ω to 19,99 kΩ
±7.5% ±3 digits (±10% at >0.5 ohms and ±0.05 ohm at <0.5 ohms for
KEMA K85B requirements.
±7.5% ±3 digits (±10% at >0.5 ohms and ±0.05 ohm at <0.5 ohms for
KEMA K85B requirements.
BS 7430 (1992)
VDE 0413 Part 7 (1982)
128 Hz ±0,5 Hz
20 Ω range
200 Ω range
2 kΩ and 20 kΩ ranges
Test current (= short circuit current) is constant throughout a range.
Interference voltages of 40 V pk to pk at 50 Hz, 60 Hz, 200 Hz or 16
in the Potential circuit will have a max. effect of typically ±1% on the
reading obtained for the 20 Ω to 2 kΩ ranges. If the 'Noise' indicator is not
showing, the maximum error due to 'noise' voltage on these ranges will
not exceed 2%. In the 20 kΩ range this is reduced to 32 V pk to pk.
The loop resistance that will introduce an additional 1% error is:
20 Ω range
200 Ω range
2 kΩ and 20 kΩ ranges
BS7671 (1992)
NFC 15 -100
IEC364
10 mA a.c. r.m.s.
1 mA a.c. r.m.s.
100 µA a.c. r.m.s
4 kΩ
40 kΩ
400 kΩ
Hz