7.
Decommissioning
7.1
Change of location
¶
If the FSA 050 is passed on, all the documentation
included in the scope of delivery must be handed over
together with the unit.
¶
The FSA 050 is only ever to be transported in the
original or equivalent packaging.
¶
Unplug the electrical connection.
¶
Heed the notes on initial commissioning.
7.2
Disposal and scrapping
FSA 050, accessories and packaging should
be sorted for environmental-friendly recycling.
¶
Do not dispose FSA 050 into household
waste.
Only for EC countries:
The FSA 050 is subject to the European
directive 2012/19/EC (WEEE).
Dispose of used electrical and electronic
devices, including cables, accessories and
batteries, separately from household waste.
¶
Make use of the local return and collection
systems for disposal.
¶
Proper disposal of FSA 050 prevents
environmental pollution and possible health
hazards.
Robert Bosch GmbH
Decommissioning | FSA 050 | 35
8.
Technical data
i
All the values given are referenced to a temperature
of 20 °C.
Insulation analysis
i
The specifications only apply in conjunction with
the remote sensor and the measurement leads
contained in the scope of delivery.
Range
Accuracy
1000 V
200 GΩ ±3 % ±2 positions ±0.2 % per GΩ
500 V
100 GΩ ±3 % ±2 positions ±0.4 % per GΩ
250 V
50 GΩ ±3 % ±2 positions ±0.8 % per GΩ
100 V
20 GΩ ±3 % ±2 positions ±2.0 % per GΩ
50 V
10 GΩ ±3 % ±2 positions ±4.0 % per GΩ
Function
Specification
Analog
1 GΩ for full scale deflection
display range
Short-circuit
2 mA 0 % – 50 %
current
Terminal
0 % – 20 % ±1 V (Ii <1 mA)
voltage
Test current level
1 mA for minimum insulation continuity
under load
value according to specification as per
BS7671, HD384 and IEC364, EN 61152-2,
2 mA maximum
EN 61557
0.10 MΩ to 1.00 GΩ
operating range
Leakage current
10 μA to 2000 μA
measurement
range
Leakage current
10 % ±3 positions
Voltage display
3 % ±3 positions ±0.5 % of rated voltage
Polarisation
Ratio of 10 minutes to 1 minute
index (PI)
Dielectric
Ratio of 60 s to 30 s
absorption ratio
(DAR)
Continuity measurement
Function
Specification
EN 61557
0.01 Ω to 99.9 Ω
operating range
(0 to 100 Ω on analog scale)
Accuracy
±2 % ±2 positions (0 to 100 Ω)
Voltage in
5 V ± 1 V
open circuit:
Test current
205 mA (±5 mA) (0.01 Ω to 9.99 Ω)
20 mA (±1 mA) (10.0 Ω to 99.9 Ω)
Zero adjustment
Usually 0.10 Ω
at remote
sensor tips
Zero adjustment
Up to 9.99 Ω
of line resistance
Buzzer
Variable limit: 1 Ω, 2 Ω, 5 Ω, 10 Ω, 20 Ω
en
|
1 689 989 102
2019-05-24