3-Position-Bbpr (Gfs) Models - VALPES DV 25 Manual De Instalación Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3-POSITION-BBPR (GFS) : description
The GFS version includes BBPR battery backup and 3-position versions.
BBPR battery backup:
This system insure a return to predefined position in case of power failure. The predefined position can be set close (default)
or open.
GF3 option allow actuator to be drive and stop in 3 positions. These 3 positions could be between 0° to 180°.In standard
actuators are setting in our workshop at 0° 90° 180° that's fit with standard 3 ways ball valve. Others positions still available
but customer have to price on the order witch position is request.
Actuator voltage
Battery voltage
Battery capacity
Charging current
battery charging maximum time
Electric connection
Power supply and control wiring

Ensure that the voltage indicated on the actuator ID label corresponds to the voltage supply.

Unscrew the left cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 47.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
Feedback wiring and contacts state

Unscrew the right cable gland and insert the cable.

Remove 25mm of the cable sheath and strip each wire by 8mm.

Connect the wires to the terminal strip in accordance with the diagram p. 47.

Tighten the cable gland (Ensure that it's well mounted to guaranty the proofness).
Our 3-position actuators have 3 auxiliary switches
FC1 (white cam - 5th): open position feedback - NO
FC2 (black cam - 6th) : closed position feedback - NO
FC3 (beige cam - 7th) : intermediate position feedback - NF
To adjust the position of the auxiliary contacts, make rotate the 3 superior cams by using the appropriate wrench.
The actuator is pre-set in our factory. Do not touch the two lower cams in order to avoid any malfunctioning or
even damage to the actuator.
46
100 V to 240 V AC 50/60 Hz and 100 V to 350 V DC
24 V to 30 V AC 50/60 Hz and 24 V to 48 V DC
24 V DC
Charging status feedback relay (65/66)
600 mAh
Failure feedback relay (D3/D4)
180 mA
Temperature
3,5 h
24 V DC - 1 A max
24 V DC - 3 A max
-10 °C to +40 °C
Terminals
6 & 9
4 & 8
Closed
Open
inter
Open
Open
180°
Open
Closed
DSBA3800 • Rév. 01/10/2020
EN
F4 & F9
Closed
Open
Fermé

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Dv 45Dv 75Dv 100Dv 150Dv 300

Tabla de contenido