4.1 INSTRUCTIONS FOR SAFE USE
The IP degree of protection of the interlocked socket must be maintained by using suitable cable glands and gaskets and by
fully complying with the installation rules and the relevant instructions. When other certified components are assembled in the
interlocked socket, the user must take into account any limitation indicated on the respective certificates.
The equipment used to drill the interlocked socket must be suited for the material (fibreglass-reinforced polyester) and used at
appropriate speeds in order to avoid damaging the walls. The holes must be drilled within the drillable area defined for each wall
(see Fig. 3), and they must be carried out up to standards, without any burrs. The walls preset for drilling are 5.7 mm thick. The
drilled holes are not suited for threading.
The holes for cable entry must be drilled in compliance with this manual.
Store the interlocked socket in a warehouse inside its original packaging in order to protect it from dust or humidity. Remove the
interlocked socket from its package right before its installation.
The interlocked socket must be installed intact and damage-free.
The interlocked sockets must be installed so that dust does not penetrate the socket with or without the plug inserted. To minimize
this risk, in case the socket cover is accidentally left open, the socket must be assembled and positioned at a maximum angle of
45% with respect to the vertical, with the opening facing downward.
Instructions for proper installation of the interlocked socket:
1) Read the installation use and maintenance instructions for the interlocked socket.
2) Using the fixing dimensions shown in Figure 1 , mark the positions of the fixing holes on the installation wall.
3) Drill the fixing holes on the installation wall and thread the holes (if required).
4) Remove the interlocked socket from its package, making sure that it has not been damaged during shipping.
5) Check that the cover and the base are clean and defect-free.
6) Remove the plate with all the internal elements fixed to it from the base of the interlocked socket.
7) Place the base of the interlocked socket in the assembly position on the installation wall, using any assistance necessary in
order to prevent accidents.
8) Secure the device by repeating the following operations for each fixing hole:
a) Insert the clamping screw into the fixing hole.
b) Tighten the bolt (in case of a through-hole) or tighten the clamping screw completely.
9) Make sure the fixing is secure.
10) Proceed with the assembly of the cable glands (if not preassembled) following the manufacturer's instructions.
11) Insert the plate with all the internal elements fixed to it into the base of the interlocked socket.
12) Insert the cables in the device, being careful to secure the cable armours (if applicable).
13) Proceed with the wiring according to the wiring diagram issued to the installer.
Before you close the interlocked socket:
14) Check that all foreign materials have been removed from inside the interlocked socket: do not leave these instructions inside.
15) Check that the gaskets are intact and properly installed.
16) Close the cover by duly tightening the screws in order to guarantee the IP degree of protection. The tightening torque of the
screws is 1.2 Nm.
17) Keep these instructions in a safe place for future reference.

4.2 AVAILABLE ACCESSORIES

The accessories supplied with the interlocked socket must be assembled prior to the installation of the device, by skilled personnel,
following the methods indicated in the relevant instruction sheets.
A) Kit with microswitch for plug presence check (Art. 579.0100 for 16-32-63A)
B) Auxiliary contact (1 NO contact + 1 NC contact ) (Fam. art. 590.PL00400X).
Use original, SCAME-approved accessories only.
4.3 WIRING OF THE TERMINALS
The wiring must be carried out according to the highest standards.
Use only equipment with proper size for the wiring.