NOTE The following procedure is for an IBM
representative (see page 4).
Step 1. UPS Setup
Qty.
Powerware Part Number Description
2
—
4
—
1
157604171-001
1
157604171-002
4
—
8
—
2
157604172-001
4
—
1
164201357
1
164201356
1.
Attach the supplied mounting handles to the
mounting brackets.
NOTE The UPS and optional Extended Battery Modules
(EBMs) MUST be installed at the bottom of the rack. If placed
in a rack with existing equipment, the rack must be
reconfigured to allow the UPS installation at the bottom of
the rack.
NOTE The EBMs must be installed below the UPS.
2.
Install the clip nuts over the holes on the back of the
rack.
NOTE The clip nuts for the first set of rails go over the holes
in position 2 and 4. If you are installing additional rails, the
next set of clip nuts should be placed 4 and 6 holes above the
last installed clip nut.
Powerware
5125 (9910 P33) Quick Start for IBM
®
5125 (9910 P33) Q
IBM A
FOR
PPLICATIONS
9
pSeriesZ rack only. If you have another type of rack, contact your service
Mounting Handles
Mounting Handle Screws
Left Fixed Mounting Rail Assembly
Right Fixed Mounting Rail Assembly
10-32 Clip Nuts
10-32 1/22 Pan-Head Screws
Rear Hold-Down Brackets
10-32 1/22 Flat-Head Screws
Powerware 4-Post Rail Kit User's Guide
Powerware 5125 Installation Guide for IBM Applications
Applications : 164950139 B
®