After having connected the heat pump to the pool water circuit system trough a suitable
by-pass and having made the electrical connections by a qualified engineer, please verify
the following points:
• Appliance is in a horizontal position and on a solid ground.
• Water circuit is primed (full of water): no air inside the tubes or the heat pump
tank.
• Water circuit is well connected (no leaks and no chance of injury due to badly
fitted hydraulic couplings).
• Electrical circuit is well connected (all cables tightened correctly at terminals
and intermediate circuit breaker), insulated and earthed correctly.
• The installation requirements described previously are strictly adhered to.
• Ambient temperature is between :
-
-
• Water temperature is between 15 and 30° C (50° F and 86° F).
You can then start up your machine. Follow the instructions below in the given
order each time you start up the pool heat pump, especially at the beginning of
the swim season:
• Open the three by-pass valves and then half close the settings valve
• Start the pool pump
• Turn on the pool heat pump with the on/off switch (turn it to « I »).
The pool heat pump will work after a delay of around 2 minutes.
• Set regulation (Chapter «Regulation»).
• Set heating (Chapter «Heating»).
After a few minutes (time for circuit to heat itself) you can regulate water flow as
explained hereafter (Chapter "Water flow regulation")
After these operations, you must put your pool cover on the swimming pool and
let the heat pump work for few days in order for the water temperature to
increase to the desired temperature.
+10 and +35° C (PAC models)
-5 and +35° C
(R-PAC models) (23° F and 95° F)
(50° F and 95° F)
- 47 -